MIM-
page 22
MIM 01/0419
a.) „Triangle“ mode
In "Triangle" mode, the simulation
value increases continuously in the
increment of the parameter
"Increment value" and in the interval
"Interval time" with the "Start value".
After the amount of the parameter
"intervals", the simulation value
decreases again in the same way,
in order to increase again. This
process is repeated continuously until the set time "Sim Auto Stop Time" has
expired and the simulation ends.
b.) "Monotonic" mode
In "Monotonic" mode, the simulation
value increases continuously in the step
size of the parameter "Increment value"
and in the interval "Interval time" with the
"Start value". After the amount of
"Intervals" or the expiration of "Sim Auto
Stop Time", the simulation ends.
c.) “Static” mode
In the "Static" mode, a constant value is output for the
measured values flow and temperature. The
simulation ends after the set simulation time.
In the "static" simulation for the part quantity counter,
the counter is only changed once by the set
"increment value" after the start.
When simulating the subset counter, note that in triangle mode, the submenu
counter must be in bidirectional mode to achieve the expected effect.
Time
Simulation value
Interval time
Start value
Intervals
Increment value
Sim Autostoptime