MIM-
page 32
MIM 01/0419
Parameter table
Output 1/2 – Flow
Sub-
parameter
level 1
Sub-
parameter
level 2
Sub-
parameter
level 3
Description
Value range /
value list
Standard
value LPM
Standard
value
GPM
disabled
Output deactivated
disabled
Alarm output
Function
List
selection
Sets the basic
function
Limit function /
window function
Limit function
Output
Sets the electr.
Output
NPN/PNP/PP
NPN
switching
function
Set the log. switching
function
NO/NC
NO
threshold
Value input
Sets the switching
threshold
MB start
≤
value
≤
Full scale
1
lower
threshold
Sets the lower
threshold for window
function
Value threshold
≤
value
≤
MB start
1
hysteresis
Defines the switching
hysteresis
-9999,0
≤
value
≤
+9999,0
1
filter factor
Factor for the
switching delay
x100 ms
0x
≤
value
≤
60x 0
4-20 mA
Value 4 mA
Measured value for
4 mA output
MB-start
≤
value
≤
Wert 20 mA
0
Value 20 mA
Measured value for
20 mA output
Value 4 mA
≤
value
≤
Full
scale
100
0-20 mA
Value 0 mA
Measured value for
0 mA output
MB start
≤
value
≤
value 20 mA
0
Value 20
mA
Measured value for
20 mA output
Value for 0 mA
≤
value
≤
Full
scale
100
2-10 V
Value 2 V
Measured value for
2 V output
MB start
≤
value
≤
value 10 V
0
Value 10 V
Measured value for
10 V output
Value for 2 V
≤
value
≤
Full
scale
100
0-10 V
Value 0 V
Measured value for
0 V output
MB start
≤
value
≤
value 10 V
0
Value 10 V
Measured value for
10 V output
Value for 0 V
≤
value
≤
Full
scale
100
Frequency
output
max.
frequency
Frequency output at
"value at max. Hz"
50-1000 Hz
500 Hz
overflow
Overflow value in %
of the value
"max.frequency"
1-100 [%]
1%
Value at 0 Hz
Value at 0 Hz
MB start
≤
value
≤
value at max.
Hz
0
Value at max.
Hz
Value at "maximum
frequency"
Value for 0 Hz
<
value
≤
Full
scale
100
Control input
(only output 1)
Control function for
MIN / MAX memory
reset
OFF, memory
reset
Aus
KofiCom
Factory calibration mode on output 1
IO-Link
This mode activates the IO-Link function on output 1