RMS compact
54
The following screenshot shows an example the SerialTFTP upgrade software, in TFTP mode:
Figure 68: SerialTFTP Tool in TFTP Mode
Serial Upgrade
The serial upgrade option utilises a serial port to serial port connection between the RMS compactand the PC
running the upgrade tool.
There are a number of parameters which must be setup before the downloader can be used, as follows:
Port :
Select the Com port being used on your PC/Server
Baud:
Set the baud rate at which the serial download process runs (product dependent).
Location:
The location of the download files on your disk drive – these must be copied to a directory on
your hard disk before attempting the download process.
Product:
Select the product and variant type from the drop down menu.
•
Connect the configuration cable (NC-CFG) between the Comm port of your PC and the port labeled
‘RS232’ on your RMS Compact.
•
Ensure that the DIP switch settings on the RMS compactare as follows – DIP switch 1 UP, DIP switch 2
DOWN.
•
Disconnect the power from the RMS Compact.
The RMS compactis now ready to be upgraded:
•
On the SerialTFTP Upgrade tool screen select the UPGRADE button – this should set the
port status
to
OPEN, and display the expected checksums for this version.
•
Now re-apply the power to the RMS compact– you should see text displayed in the
Data
window of the
downloader, and the progress bar should start to increment, until the first block of data is complete, then it
will start on the next block.
•
When complete, you should see UPGRADE SUCCESSFUL displayed in the data window.
If this process fails, and the checksums do not match up, resend the data using the RESEND button on the
downloader.
Содержание RMS compact
Страница 1: ...RMS compact User Manual Version 1 0 9...