RMS compact
19
2. Change Temperature Name
3. Change Temperature Offset
4. Change Temperature Limits
5. Change Temperature OFF to ON Traps Setup
6. Change Temperature OFF to ON Traps Repeat Timers
7. Change Temperature ON to OFF Traps Setup
8. Change Temperature ON to OFF Traps Repeat Timers
9. Exit Temperature Setup
Enter choice (ESC to exit):
Figure 21 Temperature parameter Configuration
This menu enables the user to ENABLE/DISABLE temperature monitoring, change the TEXT descriptor of the
alarm, set OFFSETS, select THRESHOLD limits (this includes limits for the warning traps to indicate that a
temperature is nearing its threshold), and also to set TRAP REPEAT TIMERS.
Note
Note
Note
Note
:
The Minimum Setting for a Trap Repeat Timer is 30 seconds.
This option should display the following menu:
Knuerr RMS compact version X.X.X
Embedded Agent Setup
Temperature Lower Control Limit: -20.0
Temperature Lower Warning Limit: -20.0
Temperature Upper Warning Limit: 35.0
Temperature Upper Control Limit: 40.0
1. Change Lower Control Limit
2. Change Lower Warning Limit
3. Change Upper Warning Limit
4. Change Upper Control Limit
5. Exit Limits Setup
Enter choice (ESC to exit):
Figure 22 Temperature threshold Limits Configuration
Also, in the Temperature Parameter screen, the user is able to enable traps for off to on transitions and on to off
transitions, as well as setting timers for repeat traps if required.
The same options are available for Temperature 2 (the second temperature sensor port).
Note:
Note:
Note:
Note:
If a Temperature only sensor is being used (i.e. no humidity), then the humidity monitoring must me
MANUALLY DISABLED, in order to prevent an error reading from the RMS Compact.
Humidity Configuration
Selecting the
change Humidity 1 Settings
option in the main temp/humidity menu should display the following
menu:
Knuerr RMS Compact ver 0.1.14
Embedded Agent Setup by Sinetica
Humidity Monitor Enabled: YES
Humidty Name: Feuchte Abluft
Humidity Offset: 0.0
Sensor Type: ROHS COMPLIANT
1. Change Humidity Monitoring Flag
2. Change Humidity Name
3. Change Humidity Offset
4. Change Humidity Limits
5. Change Humidity OFF to ON Traps Setup
6. Change Humidity OFF to ON Traps Repeat Timers
7. Change Humidity ON to OFF Traps Setup
8. Change Humidity ON to OFF Traps Repeat Timers
9. Select Humidity Sensor Type