Entering system temperature setpoints and limits
The system temperature setpoints set the operational parameters and limits for the VAV
terminal unit.
The temperature setpoints include the following items.
l
Minimum cooling and maximum heating setpoints
l
Occupied and unoccupied cooling setpoints
l
Occupied and unoccupied heating setpoints
l
Changeover differential setpoint
l
Standby differential setpoint
Setting the temperature setpoints requires entering Password 2 which is described in detail
in the topic
Getting started with configuration
.
Tip:
Once the following procedure is started, all steps must be completed in order.
Procedure
Detailed steps
Sensor display
1
Start at the temperature
display.
1. Start at the temperature display.
2. Press the
and
buttons together.
l
If Password 2 is not required, the display
changes to
CNFG
.
l
If required, enter Password 2. The display
changes to
CNFG
when Password 2 is correct.
72
12S1
PSW2
OOOO
2
Select the setpoint display.
1. From the
CNFG
display, press the
or
buttons to
show
STPT
.
2. Press the
Set
Point
button to select the
CNFG
options. The
display changes to
STPT
.
3. Press the
Set
Point
button to select
STPT
. The display
changes to
MIN
.
CNFG
STPT
3
Set the minimum cooling
setpoint.
This setpoint limits the lowest temperature that a user
can enter as the active setpoint.
MIN
68O
Procedure to set the temperature setpoints
SimplyVAV
Section 4: Configuring the controllers
Revision H
23
Содержание SimplyVAV BAC-8001
Страница 1: ...SimplyVAV Application and Installation Guide Revision H ...
Страница 12: ...Section 1 About the controllers KMC Controls Inc 12 Revision H ...
Страница 48: ...Section 6 Application drawings KMC Controls Inc 48 Revision H ...
Страница 62: ...Section 7 Sequences of operation KMC Controls Inc 62 Revision H ...
Страница 72: ...Appendix A K factors KMC Controls Inc 72 Revision H ...