When the unit Occupancy state is
UNOCCUPIED
, the fan starts and runs at minimum
speed only on a call for heating. The fan starts when the Heating loop is greater than 5% and
stops when the Heating loop is less than 1%.
Illustration 7–3 Parallel fan operation
MAX FAN SPEED
MIN FAN SPEED
FAN OFF
OCCUPIED
HTG SP
ROOM TEMP INCREASE
UNOCCUPIED/
STANDBY
Reheat sequence
The SimplyVAV controllers can control four types of reheat installations.
l
l
l
l
All reheat is controlled by either the Heating loop or the Discharge Air Temp Limiting (DAT)
PID loop. Loops are described in the topic
.
l
If Discharge Air Temp Limiting is enabled, reheat is controlled by the DAT PID loop.
l
If DAT control is not enabled, reheat is controlled by the Heating loop.
In the following descriptions, the loop controlling reheat is referred to as the Reheat loop.
SimplyVAV
Section 7: Sequences of operation
Revision H
57