Procedure
Detailed steps
Sensor display
1. Press the
or
buttons to set the primary K-
factor.
2. Press the
Set
Point
button to save the entry and advance to
the next function.
4
Set the secondary VAV
terminal unit K-factor.
Not used in all models.
The K-factor is supplied by the manufacturer of the VAV
terminal unit. Typically it is on the label with the unit
airflow information.
1. Press the
or
buttons to set the secondary K-
factor.
2. Press the
Set
Point
button to save the entry and advance to
the next function.
9O4
SKFT
5
Set the mode of reheat for the
terminal unit.
Not used in all models.
1. Press the
or
buttons to choose one of the
following reheat options.
None
—Reheat is not enabled.
Staged
—Enables staged reheat.
Modulating
—The analog reheat output varies from
0-10 volts DC.
Floating
—The reheat outputs control a tristate
actuator.
Time proportional
—A 24-volt triac output controls a
thermal wax valve.
2. Press the
Set
Point
button to save the reheat option and
advance to the next function.
NONE
REHT
6
Set the fan option.
Not used in all models.
1. Press the
or
buttons to choose one of the
following fan options.
None
—No fan is connected to the controller.
Series
—The VAV unit includes a series fan.
Parallel
—The VAV unit includes a parallel fan.
2. Press the
Set
Point
button to save the fan option and
advance to the next function.
NONE
FAN
Procedure to set the box functions (continued)
Section 4: Configuring the controllers
KMC Controls, Inc.
28
Revision H
Содержание SimplyVAV BAC-8001
Страница 1: ...SimplyVAV Application and Installation Guide Revision H ...
Страница 12: ...Section 1 About the controllers KMC Controls Inc 12 Revision H ...
Страница 48: ...Section 6 Application drawings KMC Controls Inc 48 Revision H ...
Страница 62: ...Section 7 Sequences of operation KMC Controls Inc 62 Revision H ...
Страница 72: ...Appendix A K factors KMC Controls Inc 72 Revision H ...