KMC Controls
Revision E
Installation
Planning for input and output modules
20
Planning for input
and output
modules
To connect inputs or output devices to a KMD-5210 controller, use KMD-5220
input and KMD-5221 output modules. The KMD-5210 controller includes
eight universal I/O ports for up to eight KMD-5220 input modules, eight
KMD-5221 output modules or any combination of up to eight modules.
Each module connects to the controller using a flat ribbon cable. When
connecting input and output modules, use the following guidelines.
◆
Connect the first KMD-5220 input module to connector
I/O Card 1
; add
continue adding input modules from left to right
◆
Connect the first KMD-5221 output module to connector
I/O Card 8
and
continue adding output modules from right to left.
◆
Use ribbon cables no longer than 24 inches (61 cm).
◆
KMD-5221 output modules require an output transformers.
Illustration 2-8 Typical input and output module connection
Содержание KMD-5210
Страница 4: ...KMC Controls Revision E 4 ...
Страница 12: ...KMC Controls Revision E About the LAN controller Safety Considerations 12 ...
Страница 26: ...KMC Controls Revision E Installation Connecting to a Computer 26 ...
Страница 30: ...KMC Controls Revision E Operation Resetting the controller 30 ...
Страница 38: ...KMC Controls Revision E Configuration and programming System time keeping 38 ...