KMC Controls
Revision E
Installation
BACnet networks
18
Note
The controller with only one EIA–485 cable connected is normally the
end-of-line. This is also the controller where the cable shield ground is tied to
earth or a chassis ground
.
BACnet networks
The KMD-5210 LAN Controller supports an optional Class 3 Conformance
Level of the BACnet specification. The BACnet protocol is implemented using
either one or the other of the following network configurations.
◆
Ethernet 802.3 specification in KMD-5210-001
◆
MS/TP EIA–485 in KMD-5210—002.
See the section
Programming for BACnet in WinControl XL
for details on
BACnet features.
Note
The BACnet options are licensed for each controller. To upgrade a KMD-5210
controller to BACnet, contact KMC Controls for license information.
BACnet 802.3
The KMD-5210–001, the BACnet 802.3 version of the LAN controller, connects
to the LAN in the same manner as the standard LAN controller. See
The BACnet internetwork most likely will use one or more BACnet routers to
manage the BACnet internetwork and devices. The KMD-5210–001 must be
connected to the same Ethernet broadcast domain segment as at least one
BACnet router and the router must be enabled for BACnet 802.3 traffic. To
configure a KMD-5210–002 for network connections, see
.
Illustration 2-6 End-of-line termination jumper sample for a Tier 1 network
Install jumpers
Remove jumpers
Install jumpers
Содержание KMD-5210
Страница 4: ...KMC Controls Revision E 4 ...
Страница 12: ...KMC Controls Revision E About the LAN controller Safety Considerations 12 ...
Страница 26: ...KMC Controls Revision E Installation Connecting to a Computer 26 ...
Страница 30: ...KMC Controls Revision E Operation Resetting the controller 30 ...
Страница 38: ...KMC Controls Revision E Configuration and programming System time keeping 38 ...