KMD-5205 and KMD-5270 Installation and Operation
Revision J
About the controllers
Specifications
7
Logging
Trend logs
16 trend logs each supporting up to 6 analog,
digital or virtual elements or points. Trend logs
displayed as text or graphics.
Runtime logs
16 runtime logs with time and date stamp and
cumulative runtime
Custom graphics
32 system groups each of which can manage 64
points with animated and color graphics.
Requires WinControl XL Plus to view and edit
graphics.
KMD-5270 models serves the background
system group graphic to browser accessible web
pages.
Security
Six operator access levels
256 names with passwords
Alarms
Alarm buffering up to 16 alarms
On-board 68-character alarm or maintenance
text messages
Memory
Flash memory
2 megabyte non-volatile flash memory
Ram
2 megabyte with six-hour backup
Programs and program parameters are stored in
non-volatile memory.
Communication ports
Ethernet
One Ethernet 10Base-T port for KMD Tier 1 and
optional BACnet 8802.3
RS-485
Connects to either KMC Tier 2 or Modus RTU
controllers.
Connector type is removable screw terminal
block. Wire size 14–22 AWG
Serial
Serial 9-pin connector for directly connecting to
a computer serial port
or
optional external
modem for remote operation.