KMC Controls
Revision J
Configuration and programming
Setting up for BACnet networks
30
Setting up for
BACnet networks
These topics apply only to the following models:
◆
KMD-5205-006
◆
KMD-5270-001
◆
KMD-5270-006
If the controller is licensed for BACnet and connected to a BACnet network, the
controller must be configured to communicate with the network.
Detail
BACnet device settings are covered in more detail in BACstage or TotalControl
help. The BACstage and TotalControl reference guides are available also in
Adobe Acrobat format on the KMC Controls web site.
Table 4-3 BACnet settings in HCM
Setting
Description
Instance
The device instance number as assigned by the BACnet system
designer. Instance numbers are required, must be unique among all
devices on the internetwork and range from 0 to 4,194,303.
Name
A required 16-character label of the device.
Name
must be unique
among all devices on the internetwork. The set of characters used
in
Name
is restricted to printable characters.
Location
Optional information used to further identify a piece of equipment.
Description
Optional information used to further identify a piece of equipment.
APDU Timeout
Indicates the period—in milliseconds— between retransmissions of
an APDU requiring an acknowledgement for which no
acknowledgment has been received. The default value is 3000
milliseconds.
Max Master
Not applicable to KMD-5205 or KMD–5270 models.
Token Timeout
Not applicable to KMD-5205 or KMD–5270 models.