Initializing with HCM
28
8. Cycle the power to the controller. The controller can now be connected to
a network and additional programming can be performed with
WinControl XL Plus or TotalControl.
KMC digital network configuration
The entries in the table
HCM Configuration Screen setup fields
are required
for controller-to-controller communications on a either KMD Tier 1 or KMD Tier 2
networks.
Table 4-1 HCM Configuration Screen setup fields
Setting
Description
Address
Enter the address that is assigned to the controller on the KMD
Tier 1 network. Valid entries are 1–31.
Last Panel
Not applicable on any KMD-5205 or KMD-5270 models.
SubLAN A
Sets the connection speed of the Tier 2 port to which the
controller is connected. Set the baud to match the baud of the
other controllers on the Tier 2 network.
Modem
Select to indicate a modem is connect to the nine-pin serial
connector. If Modem is selected, a computer cannot be directly
connected to the nine-pin connector.
Modem String
The controller automatically transmits initialization strings for
U.S. Robotics modems. If you are using a different modem,
enter the initialization string here. This can normally be found
in the modem manual.
The default initialization string is
AT&A &B1 &C1 &D2 &H1
&K0 &R
.
Computer Port
Enter the communication speed for a PC is directly connected
to this port or the modem-to-computer baud if a modem is
connected to the controller.
SMPT IP Address
Enter the IP address of the e-mail SMTP server. This address is
required to
send e-mail with KMD-5270 models. The
address is supplied by the network system administrator.