![Klingenburg CERTO Скачать руководство пользователя страница 37](http://html1.mh-extra.com/html/klingenburg/certo/certo_documentation_1978060037.webp)
37
37
Operation instructions controller
Changes lead to increased water usage and should only be made if a hygiene inspection reveals bacterial
contamination due to standing water.
When „Normal Rinse“ is selected, the following will appear:
Normal rinse duration
The actual rinse procedure has an adjustable time duration between 10 and 1800 seconds, which is preset to
180 seconds. For half of the set time, the water conduit, filter and pumping station are rinsed with water. Then
the rinse valve under the filter will close, and only the nozzles are rinsed with water.
Air pressure rinse duration
For the pressured air hygienic rinse, the times are
freely selectable for each rinse phase.
S p ü l a r t
S p ü l a r t
N o r m a l s p ü l u n g
D r u c k l u f t s p ü l u n g
S p ü l d a u e r
L e i t u n g s s p ü l d a u .
F i l t e r s p ü l d a u e r
A u s b l a s d a u e r
1 - 1 8 0 0 s
1 8 0 s
1 - 2 5 0 s
3 0 s
1 - 2 5 0 s
1 0 s
1 - 2 5 0 s
6 0 s
Rinse Type
Normal rinse
Rinse Type
Air pressure rinse
Rinse duration
1-1800s 180s
Conduit rinse
Filter rinse duration
Blowout duration
In the first phase, the water conduit to the humidifier is rinsed with fresh water via forwards pressure through the
pumping station’s filter. The time duration should be adjusted appropriate to the lengths of the conduits.
During the second phase, the water intake is stopped, the air pressure is activated, and the filter is cleared using
oil-free pressured air. The time can be set short at 5 - 10 seconds, because the filter cup is quickly clear of water.
The last phase empties the pumping station, all nozzles, distributors and nozzle holders via magnetic valves
mounted on the additional distributor of the nozzle system to remove the water. The blowout duration is based on
the number of distributors, nozzle holders and nozzles.
After that, the rinsing valves and back-rinsing valve under the filter stay open for 30 seconds to make the system
pressure-free. This duration is not adjustable
Emptying
Duration
L e i t u n g s s p ü l d a u .
F i l t e r s p ü l d a u e r
A u s b l a s d a u e r
E n t l e e r u n g !
1 - 2 5 0 s
3 0 s
1 - 2 5 0 s
1 0 s
1 - 2 5 0 s
6 0 s
D a u e r 0 0 3 0 s
Conduit rinse
Filter rinse duration
Blowout duration