110
EVO-S, EVO-H
MODULAR AIR HANDLING UNITS
OPERATION AND MAINTENANCE MANUAL
10. EXTERNAL VERSION OF THE KLIMOR EVO AIR
HANDLING UNITS
KLIMOR EVO units can be adapted to work in outdoor con-
ditions. The differences between the roof version of the air
handling units and the standard version are specified below:
a) Housing
All gaps between the fixed panels of the cover type and the
aluminium frame are filled with sealing compound.
b) Air intake/outlet
The air intake/outlet is made as a ventilation fitting with
steering wheels and a net. Its role is to cover the air inlet/
outlet from rain, wind and solids larger than 10×10mm.
It’s screwed to the damper or the air handling unit profile.
Mounting on the front wall or other (e.g. side) wall after
equipping the air handling unit with an empty section. It is
possible to mount additional elbows or ducts.
When the inlet is mounting on the side of the unit, the sec-
tion is equipped with an a drip tray for collecting conden-
sate (rainwater).
For the facing walls of the air inlet and outlet, if the outlet
is above the inlet, additional ventilation elements (duct or
knees) should be used on one of the air direction, to elimi-
nate the possible impact of both air jets.
c) Air dampers
The shut-off dampers are mounted outside the unit. Such
location is possible by hiding the blade drive in a double al-
uminium profile. The damper actuators are covered, but the
actuators with a higher degree of protection min IP54 are
required.
d) Exchangers
Water exchangers (heaters) are equipped with anti-freeze
protection by an anti-freeze thermostat in the air (only avail-
able with the supplied complete control system).
The heater collector stubs can be led inside the unit in a way
that allows for installation of pipelines, supply and return,
through the ceiling in the space between the unit frame
or inside. It is also possible to install the exchanger control
node in an additional section.
e) Roofing
Fig. 83
Installation of air handling unit roofing
Each set has a roofing made of galvanized or coated sheet
metal, mounted to the profile.
Fig. 84
Connecting parts of the roofing
A set of roofing elements is delivered on a separate pallet.
The assembly of the roofing takes place after the unit has
been set up on the destination.
f) Control system
Control system can be supplied in external or internal design.
The IP65 outdoor control system’s switchgear is equipped
with a heater and thermostat. Inverters for mounting inside
the unit in the fan section.
Fig. 85
Preferred place of inverters in the fan block.
Fig. 86
Free spaces required by inverters
Table 32
Free spaces required by inverters
Type of inverter
Min. free space A [mm]
Installation inside the roof unit
50
Mounting outside the indoor unit
0
The AHU roofing enables walking during in-
stallation.
Fill with sealing mass before
connecting the two parts
Fill with sealing mass before
connecting the two parts
Connecting roof elements 1pcs per 1m width
of the unit
Inverter
Width of the AHU
Содержание EVO - H
Страница 60: ...SERWIS SERVICE 48 587839954 48 500087227 serwis klimor com...
Страница 118: ...SERWIS SERVICE 48 587839954 48 500087227 serwis klimor com...
Страница 119: ...EVO S EVO H KLIMOR...
Страница 124: ...122 EVO S EVO H 2 2 5 2 2 3 Technical acceptance Klimor 2 4 y o 5100 3500 0050 0021 50 1 6 3 3 1 3...
Страница 127: ...125 14 11 12 13 3 2 15 16 15 16 17 17 18 18 RR OMM KL RR ASM GUILS Klimor...
Страница 130: ...128 EVO S EVO H 25 26 c 200x200 300x200 27 27 d 0230 0090 300x200 28 28 0230 0090...
Страница 131: ...129 e 0001 0021 29 0001 A 1400 B 1900 0021 A 1700 B 1600 29 0001 0021 3 4 2 EVO 2000 5100 5610 30 13 M12 30 M12 M12...
Страница 132: ...130 EVO S EVO H 2900 a 50 31 b 150 32 c 33 2900 b c...
Страница 133: ...131 3 4 3 34 35 13 36 5100 0720 0230 0050 0230 0050 37 38 RR OMM KL RR ASM GUILS 3 5 3 5 1 110 EN 1886 20 20...
Страница 141: ...139 43 8 1200 600 230 50 36 310 x 230 x 125 4 3 2 E G4 ISO COARSE 60 6...
Страница 142: ...140 EVO S EVO H 44 45 46 100 C 47 48 49...
Страница 143: ...141 4 3 3 SR 50 230 50 60 CA 1 2 CG 3 2 CG 3 1 CA 4 3 4 52 51...
Страница 144: ...142 EVO S EVO H 53 54 55 4...
Страница 145: ...143 56 4 3 5 G4 ISO COARSE 60 6 57 57 58 INOX 2 3 Power supply LED C 3x2 5 2x2 5 C 2x1 5...
Страница 146: ...144 EVO S EVO H 59 60 C 4 4 WH CuAl 4 8 1 4 5 EH 60 4 5 1 4...
Страница 147: ...145 4 6 GM E GZ50 LW GZ41 5 LS GZ35 B P LPG GM 4 6 1 Klimor 1 2 3 3 4 5 5 6 020 7 a b c d 0 10 e f g 5...
Страница 149: ...147 62 3 5 4 5 6 7 63 8 4 9 64 63 64 4 7 2 12 5 5...
Страница 155: ...153 UVC S UVC S KLIMOR 2 74 UVC S UVC S 4 11 RR RR 85 97 OJ MRHX OJ DRHX OJ DRHX Field Oriented Controls FOC...
Страница 157: ...155 150 4 12 1 CPR PR 6 12 50 0 C 4 13 RG 55 76 Cu Al Cu Al 23 DN63 PN Klimor Klimor 230 50...
Страница 167: ...165 4 14 2 3 4 14 3 Klimor 5 6 6 1 KT 8 100 C...
Страница 168: ...166 EVO S EVO H 7 12 PN EN 13779 2008 12 2000 24 4000 24 4000 3 6 12 30 C 130 C 4...
Страница 169: ...167 8 30 1 2 3 DX 4 5 6 7...
Страница 170: ...168 EVO S EVO H 31 CM HPM 9 9 1 a b c 015 d 9 2 90 70 C 1 6 9 3 9 4 9 5 9 6 a b 30 c d e f IP54 g...
Страница 171: ...169 10 KLIMOR EVO KLIMOR EVO a b 10 10 c IP54 d c e 83 84 f IP65 85 86 32 A 50 0 1 1...
Страница 173: ...171 11 7 11 8 11 9 91 11 10 DIN 1946 4 DIN 1946 4 DIN 1946 4 DIN 1946 4 3 I 2 4 0 8 80 20 1...
Страница 174: ...172 EVO S EVO H 11 11 m in HEPA...
Страница 175: ...173 m in HEPA EN ISO 14644 1 3...
Страница 176: ...174 EVO S EVO H 12...
Страница 177: ......