INSTALLATION INSTRUCTIONS

HM700ADISTKIT

ELECTRODE STEAM HUMIDIFIER DISTRIBUTION KIT

CAUTION

Before Servicing

1. Disconnect main power source before 

accessing internal compartments.

2. The plumbing and electrical compartments 

contain high voltage components and wiring.

Access should be limited to licensed HVAC

professionals only.

3. During and following operation of the 

humidifier, the steam components in contact

with the steam such as the cylinder, steam 

lines, steam distributors, and condensate lines

can become hot and burn if touched. Please 

consult HM700 Installation manual for 

reference.

4. Installations of humidity equipment installed by 

unqualified personnel or the use of non-

Honeywell parts and components will void 

warranty.

Steam Distributor

The HM700ADISTKIT is a remote mount, stainless steel 

steam distribution kit used with the HM700 Electrode 

Steam Humidifier. The distributor is installed in a 

ventilation duct to distribute the steam produced by the 

HM700.

The HM700ADISTKIT consists of a steam distributor, 

steam hose, condensate hose, and installation hardware.

The steam distributor should be installed as close as 

possible to the humidifier. Short steam distribution lines 

minimize condensate loss and the possibility of 

generating backpressure in the steam distribution line.

STEAM DISTRIBUTION

Steam generated by the humidifier may be introduced 

into the air in several different ways. The most common 

method for adding the steam into the air is to mount a 

steam distributor tube in a supply air duct as shown in 

Fig. 2.

STEAM LINE

The steam line between the cylinder steam outlet and the 

distributor serves two purposes: it is used as a conduit to 

transfer the atmospheric steam from the humidifier to the 

distributor, as well as providing a means to remove 

condensate. See 

n

Steam Lines and Condensate Return 

Instructions

o

 on page 2 for information on selecting 

steam lines.

CONDENSATE RETURN

Whenever steam is distributed condensate is formed in 

the distribution system. Insulating steam lines is one 

important way to reduce the amount of condensate 

formed. Steam lines are sloped so that condensate does 

not collect in the lines and create a restriction to steam 

flow. The condensate must be collected and removed 

from the system so that it does not build up and leak into 

the duct. Condensate can be returned to the HM700 fill 

cup to reduce water waste or can be fed to drain.

KIT CONTENTS:

p

Stainless steel nozzle

p

Insulated hose (5 ft.)

p

Hose support brackets

p

Screws

p

Clamps

p

Installation Instructions

TOOLS NEEDED (NOT SUPPLIED):

p

Screwdriver

p

Pliers (optional)

Содержание HM700-FIAC

Страница 1: ...Electrode Steam Humidifiers klimaireINTL klimaireINTL com 1 647 477 3333 1 646 808 0240 KLIMAIRE International www klimaireINTL com HM700 Fiac IOM Manual...

Страница 2: ...The HM700 humidifier has been designed to require very little maintenance Regular maintenance consists of checking the humidifier to ensure it is in good condition replacing the cylinder when the sof...

Страница 3: ...umidifier drain until no more water is flowing out to drain usually not more than 10 minutes 2 Turn the humidifier On Off Drain switch to off 3 Close supply water shut off valve 4 Turn off power to th...

Страница 4: ...nap red coil cap on solenoid and remove the solenoid from the valve 5 Loosen brass nut holding actuator to plastic hous ing with a wrench and disassemble actuator 6 Clean actuator components and valve...

Страница 5: ...plastic cylinder steam outlet 3 Attach color coded cylinder plugs to the corre sponding color coded cylinder pin Push down completely Connect high water sensor plug Spring loaded plugs should fit snu...

Страница 6: ...nimize condensate loss and the possibility of generating backpressure in the steam distribution line STEAM DISTRIBUTION Steam generated by the humidifier may be introduced into the air in several diff...

Страница 7: ...ent 4 All bends should be done in large radius 12 in minimum Steam hose will soften when and may kick if too tight a radius is used which can cause a blockage and excessive back pressure 5 Horizontal...

Страница 8: ...Fig 1 Condensate return Fig 2 HM700 Duct Distributor Installation 1 746 2 0 14 x 3 344 6 89 746 2 0 14 27 68 37 3 6 344 6 89 2 78 2 8 746 2 0 14 Mount distributor nozzle to side of duct...

Страница 9: ...urements in inches mm Fig 6 Common steam line installation errors Measurements in inches mm 1 1 2 191 36 2 2 1 2 191 6 97 32 27 8 0 2 7944368 6 87 1 2 191 322 8 78 1 37 83 0 2 6 32 27 8 0 2 1 2 191 1...

Страница 10: ...n Honeywell parts and components will void warranty Included in the Box p Drain Valve p Clip p Phillips Head Screws p Wiring Harness p Installation Instructions Tools Needed p Screwdriver p Pliers opt...

Страница 11: ...nts will void warranty Included in the Box p Fill Valve p Tie Wrap p Clip p Phillips Head Screws p Installation Instructions Tools Needed p Screwdriver p Pliers Step 1 Refer to the humidifier operatin...

Страница 12: ...lace new Fill Valve into port 3 Use provided machine screws replacing those removed in Step 3 to fasten the valve onto the wall of the unit 4 Screw fitting back onto valve Step 5 1 Place spring clamp...

Отзывы: