ELECTRODE HUMIDIFIER CYLINDER REPLACEMENT

Fig. 5. Drain Valve Actuator Assembly

Installing the New Cylinder

CAUTION

Verify Model Number

Make sure the new cylinder is the same model as 

the one that was removed. Model number is on 

top left corner of cylinder label. Only Honeywell 

HM700 replacement cylinders can be used.

1.

Insert cylinder into drain valve. Tilt cylinder forward 

and fit end of steam hose to steam outlet. Tip cylin-

der back into place.

2.

Tighten hose clamp, being careful not to over-

tighten and crush the plastic cylinder steam outlet.

3.

Attach color-coded cylinder plugs to the corre-

sponding color-coded cylinder pin. Push down 

completely. Connect high water sensor plug.

Spring-loaded plugs should fit snugly onto the cyl-

inder pin. Replace if they are loose or damaged.

4.

Replace the humidifier cover and secure with two 

screws.

5.

Turn on power to humidifier with the external dis-

connect.

6.

Open supply water shut off valve.

7.

Turn the humidifier On/Off /Drain switch to On.

NOTE: The HM700 has a re-usable tie strap to

secure the cylinder for transit as well 

as home installation. This must be 

removed or loosened to remove the 

cylinder. Secure when new cylinder is 

installed.

1

70)):)%2(
730)23-(

746-2+
238)36-)28%8-32

4092+)6

%'89%836

Содержание HM700-FIAC

Страница 1: ...Electrode Steam Humidifiers klimaireINTL klimaireINTL com 1 647 477 3333 1 646 808 0240 KLIMAIRE International www klimaireINTL com HM700 Fiac IOM Manual...

Страница 2: ...The HM700 humidifier has been designed to require very little maintenance Regular maintenance consists of checking the humidifier to ensure it is in good condition replacing the cylinder when the sof...

Страница 3: ...umidifier drain until no more water is flowing out to drain usually not more than 10 minutes 2 Turn the humidifier On Off Drain switch to off 3 Close supply water shut off valve 4 Turn off power to th...

Страница 4: ...nap red coil cap on solenoid and remove the solenoid from the valve 5 Loosen brass nut holding actuator to plastic hous ing with a wrench and disassemble actuator 6 Clean actuator components and valve...

Страница 5: ...plastic cylinder steam outlet 3 Attach color coded cylinder plugs to the corre sponding color coded cylinder pin Push down completely Connect high water sensor plug Spring loaded plugs should fit snu...

Страница 6: ...nimize condensate loss and the possibility of generating backpressure in the steam distribution line STEAM DISTRIBUTION Steam generated by the humidifier may be introduced into the air in several diff...

Страница 7: ...ent 4 All bends should be done in large radius 12 in minimum Steam hose will soften when and may kick if too tight a radius is used which can cause a blockage and excessive back pressure 5 Horizontal...

Страница 8: ...Fig 1 Condensate return Fig 2 HM700 Duct Distributor Installation 1 746 2 0 14 x 3 344 6 89 746 2 0 14 27 68 37 3 6 344 6 89 2 78 2 8 746 2 0 14 Mount distributor nozzle to side of duct...

Страница 9: ...urements in inches mm Fig 6 Common steam line installation errors Measurements in inches mm 1 1 2 191 36 2 2 1 2 191 6 97 32 27 8 0 2 7944368 6 87 1 2 191 322 8 78 1 37 83 0 2 6 32 27 8 0 2 1 2 191 1...

Страница 10: ...n Honeywell parts and components will void warranty Included in the Box p Drain Valve p Clip p Phillips Head Screws p Wiring Harness p Installation Instructions Tools Needed p Screwdriver p Pliers opt...

Страница 11: ...nts will void warranty Included in the Box p Fill Valve p Tie Wrap p Clip p Phillips Head Screws p Installation Instructions Tools Needed p Screwdriver p Pliers Step 1 Refer to the humidifier operatin...

Страница 12: ...lace new Fill Valve into port 3 Use provided machine screws replacing those removed in Step 3 to fasten the valve onto the wall of the unit 4 Screw fitting back onto valve Step 5 1 Place spring clamp...

Отзывы: