INSTALLATION INSTRUCTIONS

Electrode Humidifier Drain Valve 

Replacement

HM700ADVALVE

CAUTION

Before Servicing

1. Disconnect main power source before accessing

internal compartments.

2. The plumbing and electrical compartments contain

high voltage components and wiring. Access should 

be limited to licensed HVAC professionals only.

3. During and following operation of the humidifier, the

steam components in contact with the steam such 

as the cylinder, steam lines, steam distributors, and 

condensate lines can become hot and burn if 

touched. Please consult HM700 Installation manual 

for reference.

4. Installations of humidity equipment installed by

unqualified personnel or the use of non-Honeywell 

parts and components will void warranty.

Included in the Box

p

Drain Valve

p

Clip

p

Phillips Head Screws

p

Wiring Harness

p

Installation Instructions

Tools Needed

p

Screwdriver

p

Pliers (optional)

To Replace the Drain Valve

Refer to the humidifier operating manual if necessary.

1.

Drain cylinder.

2.

Turn off the unit when the cylinder is empty.

3.

Disconnect power to the unit.

4.

Remove cylinder.

5.

Disconnect spade terminals from the drain valve.

6.

Remove the two screws holding the valve to the drain

pan.

7.

Squeeze the tabs of the spring clamp holding the hose

to the drain valve and slide it up the hose. Pull hose

from drain valve.

8.

Drain valve can be removed and replaced with new one.

9.

Reverse steps above to install drain valve.

NOTE: New screws and hose clamp provided.

Fig. 1. Drain valve.

'=0-2()64368
%2(36-2+

+6392(
;-6)

730)23-(

74%()
'322)'8367

&6%77298
%'89%836

7'6);7

,37)%2(
,37)'0%14

1

Содержание HM700-FIAC

Страница 1: ...Electrode Steam Humidifiers klimaireINTL klimaireINTL com 1 647 477 3333 1 646 808 0240 KLIMAIRE International www klimaireINTL com HM700 Fiac IOM Manual...

Страница 2: ...The HM700 humidifier has been designed to require very little maintenance Regular maintenance consists of checking the humidifier to ensure it is in good condition replacing the cylinder when the sof...

Страница 3: ...umidifier drain until no more water is flowing out to drain usually not more than 10 minutes 2 Turn the humidifier On Off Drain switch to off 3 Close supply water shut off valve 4 Turn off power to th...

Страница 4: ...nap red coil cap on solenoid and remove the solenoid from the valve 5 Loosen brass nut holding actuator to plastic hous ing with a wrench and disassemble actuator 6 Clean actuator components and valve...

Страница 5: ...plastic cylinder steam outlet 3 Attach color coded cylinder plugs to the corre sponding color coded cylinder pin Push down completely Connect high water sensor plug Spring loaded plugs should fit snu...

Страница 6: ...nimize condensate loss and the possibility of generating backpressure in the steam distribution line STEAM DISTRIBUTION Steam generated by the humidifier may be introduced into the air in several diff...

Страница 7: ...ent 4 All bends should be done in large radius 12 in minimum Steam hose will soften when and may kick if too tight a radius is used which can cause a blockage and excessive back pressure 5 Horizontal...

Страница 8: ...Fig 1 Condensate return Fig 2 HM700 Duct Distributor Installation 1 746 2 0 14 x 3 344 6 89 746 2 0 14 27 68 37 3 6 344 6 89 2 78 2 8 746 2 0 14 Mount distributor nozzle to side of duct...

Страница 9: ...urements in inches mm Fig 6 Common steam line installation errors Measurements in inches mm 1 1 2 191 36 2 2 1 2 191 6 97 32 27 8 0 2 7944368 6 87 1 2 191 322 8 78 1 37 83 0 2 6 32 27 8 0 2 1 2 191 1...

Страница 10: ...n Honeywell parts and components will void warranty Included in the Box p Drain Valve p Clip p Phillips Head Screws p Wiring Harness p Installation Instructions Tools Needed p Screwdriver p Pliers opt...

Страница 11: ...nts will void warranty Included in the Box p Fill Valve p Tie Wrap p Clip p Phillips Head Screws p Installation Instructions Tools Needed p Screwdriver p Pliers Step 1 Refer to the humidifier operatin...

Страница 12: ...lace new Fill Valve into port 3 Use provided machine screws replacing those removed in Step 3 to fasten the valve onto the wall of the unit 4 Screw fitting back onto valve Step 5 1 Place spring clamp...

Отзывы: