Steam Lines and Condensate Return Instructions

The following instructions must be followed for installation of steam lines for the HM700. Failure to use recommended 

material and exceeding maximum recommended length in Table 4, or failure to follow any other steam line installation 

instructions will result in improper operation and could void the warranty.

Table 1. Recommended Steam Line Material for HM700 Duct.

*

 The use of steam line other than copper, stainless steel tube or Honeywell supplied steam line will void the warranty

and may adversely affect the operation of the humidifier.

*

 When using copper or stainless steel tubing (other than the supplied tubing), insulation is recommended due to high

temperature safety as well as reduced condensate.

CAUTION

Plumbing to be performed by licensed HVAC 

professionals only.

Drain water from humidifier can be very hot. Do 

not drain to public sink.

All plumbing work should be done according to 

local plumbing code.

CAUTION

Installation

Do not mount in area where freezing can occur.

Do not mount on floor.

Humidifiers produce steam at atmospheric 

pressure. No devices which could block steam 

output should be connected to the steam outlet.

Steam lines must be installed so that no restriction 

can produce backpressure in the humidifier.

Regardless of selecting on/off or modulating 

control method, Honeywell humidifiers must 

have a closed circuit across its on/off security 

loop control terminal to operate. Honeywell 

highly recommends the use of a duct high limit 

humidistat.

Steam Line Installation

1.

Honeywell steam hose should only be used on 

short steam runs (under 15 feet).

2.

Ensure that no condensate produced in the steam

line will remain trapped. Steam naturally flows 

upward and condensate naturally flows downward.

3.

Ensure steam line properly supported so that no 

sags or dips are present.

4.

All bends should be done in large radius 12 in. 

minimum. Steam hose will soften when and may 

kick if too tight a radius is used which can cause a 

blockage and excessive back pressure.

5.

Horizontal runs of steam must rise 2 in. per foot 

(10º) when flow is going upwards away from the 

humidifier, or fall 1/2 in. per foot (2º) when flow is

going downwards away from the humidifier.

Condensate Return Guidelines For Main 

Steam Lines

1.

Use vertical condensate leg of distributor only. Do 

not over-tighten clamp.

2.

Condensate traps on steam mains must be located 

at all low points in the system, at each elevation

change and or directional change.

3.

Horizontal runs of steam must rise 2 in. per foot

(10º) when flow is going upwards away from con-

densate trap, and fall 1/2 in. per foot (2º) when flow

is going downwards towards a condensate trap.

4.

In a horizontal run of the steam main, condensate 

traps must be located at regular intervals.

5.

The condensate trap itself is a section of piping con-

nected to the bottom of the main. A full size tee 

must be used to create a condensate trap to allow 

the condensate to fall away from the steam flow.

6.

Vertical drop of the condensate trap should be 

1.5 times the diameter of the steam main but no 

less than 12 in.

7.

A p-trap should be installed at the bottom of the 

condensate trap. The center to center trap height

should be 2 in. greater than duct static pressure 

(see Figure 1).

To return condensate for HM700, insert copper tube 

(supplied with equipment) half way into the condensate 

opening of the fill cup along with the spring clamp 

(supplied with equipment).

Insert the condensate hose into the condensate return 

hole at the top of the unit, and over the copper tube. 

Fasten in place with the spring clamp.

Voltage

Steam Output

Material

*

Maximum 

Steam Line 

Length

Possible Losses

Minimum 

Airflow CFM

Max Static 

Pressure

lbs/hr

(kg/hr)

Steam 

Hose

MED-L 

Copper 

Tube

Stainless 

Steel Tube

ft

(m)

lbs/hr

(kg/hr)

110/120V

3.85

(1.75)

7/8 in.

3/4 in.

0.875 x 

0.049W

7

(2)

0.5

(0.2)

115

3.0 in. w.c.

220/240V

7.7

(3.5)

12

(3.5)

1.5

(0.7)

230

Содержание HM700-FIAC

Страница 1: ...Electrode Steam Humidifiers klimaireINTL klimaireINTL com 1 647 477 3333 1 646 808 0240 KLIMAIRE International www klimaireINTL com HM700 Fiac IOM Manual...

Страница 2: ...The HM700 humidifier has been designed to require very little maintenance Regular maintenance consists of checking the humidifier to ensure it is in good condition replacing the cylinder when the sof...

Страница 3: ...umidifier drain until no more water is flowing out to drain usually not more than 10 minutes 2 Turn the humidifier On Off Drain switch to off 3 Close supply water shut off valve 4 Turn off power to th...

Страница 4: ...nap red coil cap on solenoid and remove the solenoid from the valve 5 Loosen brass nut holding actuator to plastic hous ing with a wrench and disassemble actuator 6 Clean actuator components and valve...

Страница 5: ...plastic cylinder steam outlet 3 Attach color coded cylinder plugs to the corre sponding color coded cylinder pin Push down completely Connect high water sensor plug Spring loaded plugs should fit snu...

Страница 6: ...nimize condensate loss and the possibility of generating backpressure in the steam distribution line STEAM DISTRIBUTION Steam generated by the humidifier may be introduced into the air in several diff...

Страница 7: ...ent 4 All bends should be done in large radius 12 in minimum Steam hose will soften when and may kick if too tight a radius is used which can cause a blockage and excessive back pressure 5 Horizontal...

Страница 8: ...Fig 1 Condensate return Fig 2 HM700 Duct Distributor Installation 1 746 2 0 14 x 3 344 6 89 746 2 0 14 27 68 37 3 6 344 6 89 2 78 2 8 746 2 0 14 Mount distributor nozzle to side of duct...

Страница 9: ...urements in inches mm Fig 6 Common steam line installation errors Measurements in inches mm 1 1 2 191 36 2 2 1 2 191 6 97 32 27 8 0 2 7944368 6 87 1 2 191 322 8 78 1 37 83 0 2 6 32 27 8 0 2 1 2 191 1...

Страница 10: ...n Honeywell parts and components will void warranty Included in the Box p Drain Valve p Clip p Phillips Head Screws p Wiring Harness p Installation Instructions Tools Needed p Screwdriver p Pliers opt...

Страница 11: ...nts will void warranty Included in the Box p Fill Valve p Tie Wrap p Clip p Phillips Head Screws p Installation Instructions Tools Needed p Screwdriver p Pliers Step 1 Refer to the humidifier operatin...

Страница 12: ...lace new Fill Valve into port 3 Use provided machine screws replacing those removed in Step 3 to fasten the valve onto the wall of the unit 4 Screw fitting back onto valve Step 5 1 Place spring clamp...

Отзывы: