III.
Maintenance intervals in accordance with the VDMA
Explanation
yearly
½ -
yearly
if neces-
sary
Com-
ment
Compressor
1
Check outside for dirt, damage and corrosion
x
x
2
Check for fixing and running noises
x
3
Measure suction pressure
x
4
Measure the suction gas temperature upstream
of the compressor
x
5
Measure compression end temperature at the
discharge connection socket
x
6
Check oil level
x
7
Check oil for acid content (acid test)
x
8
Oil change
x
9
Check the function of the crankcase heater
x
10 Check the function of the output control
x
11 Check refrigerant side for leaks
x
12 Check high/low pressure switching device
x
Air-cooled condenser
20 Check outside for dirt, damage and corrosion
x
x
21 Measure the condensing temperature
x
22 Measure the undercooling temperature at the
condenser outlet on the refrigerant side
x
23 Measure the medium temperature at the
condenser inlet and outlet
x
24 Check the function of the condensation pressure
control
x
25 Check refrigerant side for leaks
x
Evaporator
30 Check outside for dirt, damage and corrosion
x
31 Determine
the
refrigerant
overheating
temperature
x
32 Measure the medium temperature at the
evaporator inlet and outlet
x
33 Determine the frost protection temperature
(freezing point) of the heat transfer media
x
34 Check the water and refrigerant side for leaks
x
Содержание vBoxX 10
Страница 1: ...Vario Line vBoxX 6 vBoxX 8 vBoxX 10 vBoxX 12 vBoxX 15 vBoxX 18 vBoxX 24 vBoxX 28 Instruction Manual ...
Страница 16: ...16 82 83000602 Ke ...
Страница 65: ...65 82 83000602 Ke I Overview of the menu levels Main structure ...
Страница 66: ...66 82 83000602 Ke Status ...
Страница 67: ...67 82 83000602 Ke Parameters ...
Страница 68: ...68 82 83000602 Ke ...
Страница 69: ...69 82 83000602 Ke hidden ...
Страница 70: ...70 82 83000602 Ke ...
Страница 71: ...71 82 83000602 Ke ...
Страница 82: ...82 82 83000602 Ke V EC Declaration of Conformity ...