6.2.6.
External installations
In general a free pressure of 5 Pa is available for external installations. Malfunctions can occur if
this is not ensured.
Figure 10
shows a layout with which you can implement a system with
rectangular ducts and comply with the required free pressure. The duct system consists of a straight
piece of duct [1], a 90° bend [2] and another straight piece of duct [3]. The ducts are made of
steel sheet, the duct cross-section is to be adjusted to the machine footprint. The straight duct
pieces [1] and [3] are each 2 metres long maximum. The 90° bend [2]
has a pressure loss
coefficient of ζ
≤ 0.2. The system designed is responsible for sealing and mechanical fixing of
external installations.
Figure 10: Waste air duct by way of example
For duct systems with a pressure loss greater than 5 Pa an external ventilation system with variable
air quantity must be provided. Please contact our KKT chillers service team (see
Table 1: Contact
details)
.
6.2.7.
Process level
The chiller must not be installed more than 500 mm below the process level. There is a risk that if
the chiller is not in use the cold water can drain via the internal tank. If this is nonetheless
necessary, the Level package option (
3.26 Level
package
) must be installed.
1
2
3
Содержание vBoxX 10
Страница 1: ...Vario Line vBoxX 6 vBoxX 8 vBoxX 10 vBoxX 12 vBoxX 15 vBoxX 18 vBoxX 24 vBoxX 28 Instruction Manual ...
Страница 16: ...16 82 83000602 Ke ...
Страница 65: ...65 82 83000602 Ke I Overview of the menu levels Main structure ...
Страница 66: ...66 82 83000602 Ke Status ...
Страница 67: ...67 82 83000602 Ke Parameters ...
Страница 68: ...68 82 83000602 Ke ...
Страница 69: ...69 82 83000602 Ke hidden ...
Страница 70: ...70 82 83000602 Ke ...
Страница 71: ...71 82 83000602 Ke ...
Страница 82: ...82 82 83000602 Ke V EC Declaration of Conformity ...