76 / 82
83000602.Ke
833
uPC hot gas temp.
Hot gas temperature is
outside the allowable range.
Difference between the
low pressure and high-
pressure side is too large.
Superheating too high.
Refrigerant quantity too
small.
Clean the condenser
and filter. Check the
function of the fan.
Check the cooling
water circuit. Install the
cover panels. Press the
Reset button and
acknowledge at the
display.
834
uPC press. diff. min
The pressure difference is
smaller than that needed
for lubrication of the
compressor.
Compressor does not
develop any pressure
Contact KKT chillers
service department.
835
uPC compr. fails to start
Compressor has attempted
to start, but could not start
up.
One or several of the
above-named alarms
has/have occurred.
manual reset in the
Error menu
836
uPC comp. envelope
Compressor exceeds the
allowed time of 60s, for
running outside the
envelope.
impermissible operating
state
manual reset in the
Error menu
841
EEV superheat low
The superheating value has
fallen below the minimum
limit.
Superheating too low
Reset takes place
automatically
842
EEV MOP
The maximum allowable
evaporation pressure (MOP)
has been exceeded.
Evaporation temperature
too high
Reset takes place
automatically
843
EEV suction temp low
The suction gas
temperature has fallen
below the minimum
allowable value.
Suction gas temperature
too low
Reset takes place
automatically
845
EEV group fault
An error has occurred at the
expansion valve.
one or several of the
above 3 messages in
relation to the expansion
valve (EEV) has/have
occurred
Reset takes place
automatically
851
INV general alarm
Communication with the
inverter is disrupted.
The power supply has
been interrupted.
Interface cable not
connected.
Check the power
supply of the inverter.
Check whether data
LED flashes yellow.
Check the wiring.
852
Inverter communic.
General inverter alarm
one or several of the INV
messages listed below
is/are queued
see below
901
INV overcurrent
max. power consumption
exceeded
sudden load increase,
acceleration during start-
up phase too high,
deceleration too fast
Contact KKT chillers
service department.
902
INV motor overload
Motor overload
max. motor current
exceeded beyond the
allowed period
Contact KKT chillers
service department.
903
INV overvoltage
max. DC voltage of the
intermediate circuit
exceeded
excessive speed
reduction, current surges
in the voltage supply
Contact KKT chillers
service department.
904
INV undervoltage
DC voltage of the
intermediate circuit has
fallen below the minimum
insufficient power supply,
internal inverter error
Contact KKT chillers
service department.
905
INV Drive over T
max. temperature of the
inverter exceeded
cooling air supply to the
inverter is too low,
temperature in the control
cabinet is too high
Contact KKT chillers
service department.
Содержание vBoxX 10
Страница 1: ...Vario Line vBoxX 6 vBoxX 8 vBoxX 10 vBoxX 12 vBoxX 15 vBoxX 18 vBoxX 24 vBoxX 28 Instruction Manual ...
Страница 16: ...16 82 83000602 Ke ...
Страница 65: ...65 82 83000602 Ke I Overview of the menu levels Main structure ...
Страница 66: ...66 82 83000602 Ke Status ...
Страница 67: ...67 82 83000602 Ke Parameters ...
Страница 68: ...68 82 83000602 Ke ...
Страница 69: ...69 82 83000602 Ke hidden ...
Страница 70: ...70 82 83000602 Ke ...
Страница 71: ...71 82 83000602 Ke ...
Страница 82: ...82 82 83000602 Ke V EC Declaration of Conformity ...