5)  Three-phase generating set

Balance three phases during the operation. Stop the engine for check if the 

tolerances exceed 20%. Be sure to keep the tolerance among three phases less 

than 20%.

The load for each phase must below the rated load as well as the current must 

less than rated current.

A, B, C, D (or U, V, W, N) phase arrangement should be from left to right, or 

clockwise.

Concerning starting the three phases asynchronous motors, first start the 

heavy-duty motors, and then start the light-duty motors.

 If overloading of the circuit trips the AC circuit protector, reduce the electrical 

load on the circuit, and wait a few minutes before resuming operation.

CAUTION

6. STOP PROCEDURE

1. Set the main switch to OFF.

2. Turn the breaker to the OFF.

3. Turn the start switch to the STOP position after running for 1-3 minutes with 

zero load, then the generator stopped.

 First disconnect the unit and load, then stop the generator. 

CAUTION

1. Maintenance Schedule

Check and clean    

replace

9. MALFUNCTION AND COUNTERMEASURES

1000

50

250

500

First

First

Check fuel, drain out sediment and impurity

Check & service item

Check engine oil  

Check the cooling water 

Check fan belt

Check battery electrolyte

Check for water or oil leakage

Check the loosen assembly 

Check the exhaust color 

Replace engine oil 

Replace oil filter element

Clean air cleaner element

Clean the radiator

Replace seal ring of fuel filter element

Daily check

E

n

g

in

e

Check battery electrolyte density 

Check meters and warming light

Содержание KDE12EA

Страница 1: ...WUXI KIPOR POWER CO LTD GENERATOR R Single phase KDE12EA KDE12STA Three phase KDE12EA3 KDE12STA3...

Страница 2: ......

Страница 3: ...it 3 For information about the engine operation and maintenance please see our engine s manual 4 Laymen especially the children can not realize the danger they should keep away from the generator 5 Pl...

Страница 4: ...Servicing 4 Warm up Procedure 5 Starting up Procedure and running 6 Stop Procedure 7 The Functions of the Digital Panel 8 Electrical appliance 9 Malfunction and Countermeasures 10 Simplified Troubles...

Страница 5: ...ntinuous running E Open frame type ST Super silence Rotation Shaft Steel Connection E 200 ST 310 340 Transistorized self excitation and constant voltage AVR Rated Frequency Hz Rated Power KVA Max Powe...

Страница 6: ...the working hours in noisy condition Furthermore the sound exposure level varies among different countries The conditions of generator rated output Altitude 0 m Ambient temperature 25 Relative humidi...

Страница 7: ...in the cable is bigger than the allowable current it will become over hot and the cable will be burnt If the cable is long and thin the input voltage of the electric appliance will be not enough caus...

Страница 8: ...s Start the engine after closing the door for safety and noise control 2 2 Initial start check CAUTION Stop the engine at once and check for the fault if the warning lamps light CAUTION Check the unit...

Страница 9: ...e engine oil 2 Check the cooling water in radiator 3 Check the fuel 4 Check the fuel pipe 5 Check the battery voltage 6 Check the grounding protection 7 Check the water leakage and oil leakage 8 Check...

Страница 10: ...to avoid lacking of engine oil to cause fault inspect the oil level and add engine oil if necessary CAUTION Radiator Be careful of the hot radiator It s very dangerous to open the radiator cover when...

Страница 11: ...on or replacement of the belt 4 Check the fuel Check the fuel level if normal before running the generator Often open the drain plug in the fuel tank to drain the sediment and impurity CAUTION Tighten...

Страница 12: ...same with the factory setting 1 Sampling wire disconnects 2 Abnormal frequency Too high or too low 3 Abnormal fuel system the engine rotating speed is unstable Check the fuel system P 02 Check the vo...

Страница 13: ...Reason Bad voltmeter Bad AVR Loading short circuit Rotor circuitry break Engine circuitry is burnt Bad voltmeter Bad AVR Loading is over Generator cable is burnt Rotation speed is too low Bad voltmete...

Страница 14: ...with bad matter such as fuel oil cooling water solvent filter and battery according to the law 12 Shut down the power after removing the battery cathodal wire when checking and maintaining generator...

Страница 15: ...or before start 2 Judge and elimininate troubles Start motor run but doesn t start Start motor doesn t run or it s speed is so slow Ambient temperature is very low Battery leakage Battery unclamped or...

Страница 16: ...e careful to fill fuel and prevent fuel overflowing Wipe up the overflowing fuel immediately Flame and fire are forbidden near the generator CAUTION This guide is intended to give brief information fo...

Страница 17: ...es will be burned out and damaged 4 Connect the equipment to the generating set in order For the matter of the motor load firstly the heave duty motor should be connected and then the light duty motor...

Страница 18: ...resuming operation CAUTION 6 STOP PROCEDURE 1 Set the main switch to OFF 2 Turn the breaker to the OFF 3 Turn the start switch to the STOP position after running for 1 3 minutes with zero load then th...

Страница 19: ...abinet Converter cabinet Halide lamp Projection lamp 15 Knob function ITEM switch the content of display the content include battery voltage running time output frequency output current generator volt...

Страница 20: ...ltage Indicating generator voltage Generator running Indicating the existence of electrical power Running trouble Indicating running trouble check it according to the code map list The indication lamp...

Отзывы: