017904-04 BioFicient 4-6 Installation Manual
8
INSTALLATION
1.
EXCAVATE A HOLE & LAY CONCRETE BED
Approximate dimensions
For DRY CONDITIONS excavate a hole to appropriate depth allowing minimum clearance on all sides and
base of the unit of 200mm and level the base.
For WET CONDITIONS excavate a hole at least 300mm deeper than the tank, for lean mix concrete and hard-
core base. Allow for tank width plus at least 400mm with additional allowance for any necessary shuttering.
De-water the excavation using suitable pumping equipment. Ensure that the pump discharge does not
saturate the ground in the immediate vicinity. The installer should ensure that the base is adequate to
support the weight of the tank and its contents. Place a sheet of polythene over the hard-core and up the
sides of the excavation before putting in the concrete cradle.
For UNSTABLE BASE of the excavation, i.e. running sand or similar, excavate an additional 250-300mm below
concrete levels and fill up with compacted hard-core.
A base of at least 150 - 200mm of lean mix concrete should be provided. (FOR CONCRETE SPEC. SEE BELOW).
It is recommended to back fill with C25 SEMI-DRY MIX
GENERAL CONCRETE SPECIFICATION
IN ACCORDANCE WITH BS EN 206-1 (BS 8500-1)
TYPE OF MIX
(DC) DESIGN
PERMITTED TYPE OF CEMENT
BS 12 (OPC): BS 12 (RHPC): BS 4027 (SRPC)
PERMITTED TYPE OF AGGREGATE
(coarse & fine)
BS 882
NOMINAL MAXIMUM SIZE OF AGGREGATE
20 mm
GRADES:
C25 /30
C25 /30
C16 /20
REINFORCED & ABOVE GROUND WITH HOLDING
DOWN BOLTS
REINFORCED (EG. FOR HIGH WATER TABLE)
UNREINFORCED (NORMAL CONDITIONS)
MINIMUM CEMENT
CONTENT
C30
C20
270 - 280 Kg/M
3
220 - 230 Kg/M
3
SLUMP CLASS
S1 (25mm)
RATE OF SAMPLING
READY MIX CONCRETE SHOULD BE SUPPLIED
COMPLETE WITH APPROPRIATE DELIVERY TICKET IN
ACCORDANCE WITH BS EN 12350-1
NOTE: STANDARD MIXES SHOULD NOT BE USED WHERE SULPHATES OR OTHER AGGRESSIVE CHEMICALS
EXIST IN GROUND WATER
MODEL
DIAMETER/
WIDTH
(mm)
LENGTH
(mm)
INLET
INVERT*
(mm)
OUTLET
INVERT**
(mm)
INSTALLATION
DEPTH**
(mm)
Bioficient 4
1920
3230
500
630
2300
Bioficient 5
1920
4390
500
630
2300
Bioficient 6
1920
6220
500
630
2300
* based on 500 mm invert