16
017904-04 BioFicient 4-6 Installation Manual
SLUDGE RETURN SOLENOID RUN AND PAUSE ANALOGUE TIMER SETTING (IF FITTED)
‘’ON’’ INDICATOR
‘’OFF’’ INDICATOR
TIME ON CONTROL REGULATOR
TIME OFF CONTROL REGULATOR
SOLENOID CONNECTION
The timer should be factory set at the correct settings.
Factory settings are: 5 minutes for timer ‘’ON’’ and 1 hour for timer ‘’OFF’’.
COMPLETING THE INSTALLATION
(refer to Control Panel illustration on page 13.).
1.
Plug the lead from the battery into the small white socket in the top right corner of the PCB marked
“BATTERY HEADER”.
2.
Power & Pressure Failure Detection System (where applicable) - Using a small screwdriver, push switch 11 to
the ON position.
3.
Installation of High Level Alarm (where applicable) - Remove the link in the terminal blocks between
connections 11 & 12 (TB6) before inserting cables. Using a suitable M12 gland, feed the high-level alarm
float cable through Gland Hole 7 and terminate to connection 11 & 12 (TB6) – Red to 11 & Black to 12
.
CONTROL PANEL FAULT CODES AND FUSES
CODE
FAULT CONDITION
FUSE
Amp
F1
No power to the unit
Customer Fuse
box
N/A
F2
The blower pressure has failed
N/A
N/A
F3
The high-level alarm has activated (where fitted)
N/A
N/A
F4
The fuse to the blower has failed
F4
3.15
F5
The fuse to the discharge pump has failed (where fitted)
F5
5.0
F6
The fuse to the chemical dosing pump has failed (where fitted)
F6
0.25
F7
The fuse to the recirculation pump has failed (where fitted)
F7
5.0
F8
The loss of rotation alarm has been activated (not applicable)
N/A
N/A
The unit has had a fault which has now corrected itself
- -
(Flashing left and right - Battery charging
N/A
N/A
Flashing left only - Battery charged)
All fuses are Time Lag HBC 20mm type