23

Vent Termination

Vent Terminal

Air Supply

Area Where Terminal Not Permitted.

A - Clearance above grade, veranda, porch, deck, or balcony 12 inches

(30cm) minimum.

1

B - Clearance to window or door that may be opened. 12 inches (30cm)

minimum for appliances 100 000 Btuh (30 kW) and lower.

C - Clearance to permanently closed window minimum 12 inches (30cm)

recommended to prevent condensation on window.

D - Vertical clearance to ventilated soffit located above the termination

within a horizontal distance of 2 feet (60cm) from the center line of
the termination. 18 inches (46cm) minimum.

E - Clearance to unventilated soffit 12 inches (30cm) minimum.

F - Clearance under veranda, porch, deck or balcony 12 inches

1

(30cm)

minimum.

2

G - Clearance from a perpendicular inside wall or outer corner to the

edge of the vent terminal plate is 3” (minimum).

H - Not to be installed above a meter/regulator assembly within 3 feet

(90cm) horizontally from the center line of the regulator.

I - Clearance to service regulator vent outlet 3 feet (91cm) minimum.

1

J - Clearance to non-mechanical air supply inlet to building or the

combustion air inlet to any other appliance 12 inches (30cm)
minimum for appliances 100,000 Btuh (30kW) and lower, 36
inches (90cm) minimum for appliances greater than 100,000 Btuh
(30kW).

K - Clearance to a mechanical air supply inlet 6 feet (1.8m) minimum.

1

L - Clearance above paved sidewalk or a paved driveway located on

public property 7 feet (2.1m) minimum.

3

M - Clearance above highest point of exit on roof 18 inches (45 cm).

N - Clearance to perpendicular wall 24 inches (60 cm).

(Recommended to prevent re-circulation of exhaust products.  For additional
requirements check local codes.)

V

NOTE: Clearances are to the edge of terminal plate, add 6-3/4” to
clearances to arrive at center line.
NOTE: Local Codes or Regulations may require different               
clearances.

Termination

It is imperative that the vent termination be located observing the
minimum clearances as shown. There must not be any obstruction such
as bushes, garden sheds, fences, decks or utility buildings within 24”
from the front of the termination plate.
Do not locate termination where excessive snow or ice build-up may
occur. Be sure to check vent termination area after snow falls and clear
to prevent accidental blockage of venting system. When using snow
blowers, make sure snow is not directed towards vent termination area.

General Venting Information

The gas fireplace is approved to be vented either through the side wall
or vertically through the roof.
This appliance is approved with Kingsman flex vent system and also
approved for use with Simpson Duravent Direct Vent System (model
DV-GS series).
Kingsman flex vent system can be used with Simpson Duravent Direct
Vent termination’s (model DV-GS series).
When using Simpson Duravent Direct Vent pipe a Kingsman/Duravent
adapter must be used to connect the fireplace to Simpson Duravent
Direct Vent pipe.
ONLY VENTING COMPONENTS SPECIFICALLY APPROVED
AND LABELLED FOR THIS FIREPLACE MAY BE USED.

Venting terminal shall not be recessed into a wall or siding.

1 - As specified in CGA B149 installation codes (1991).

2 - Only permitted if veranda, porch, deck, or balcony is fully open on a minimum of two

sides beneath the floor.

1

3 - A vent shall not terminate directly above a sidewalk or paved driveway which is located

between two single family dwellings and serves both dwellings.

Minimum clearance to combustibles on venting is 1” with the
following exceptions as follows:  Top of horizontal 1

1

/

2

”.  Top of

90 degree elbow in an enclosure over 52” is 4” without an
insulation sleeve.

Содержание MDVL30LP

Страница 1: ...or any other appliance What To Do If You Smell Gas Do not try to light any appliance Extinguish any open flame Do not touch any electrical switch Do not use any phone in your building Immediately cal...

Страница 2: ...tory However due to the high temperature silicone components the paint will cure when heat is applied to the appliance as it is first used The following information applies to the curing process to ge...

Страница 3: ...n 13 Door and Grill Installation 14 Bay Window Instructions 15 Brick Panel Installation 16 Ember Ash Bed Installation 16 Log Placement 17 18 Burner Replacement 20 Lighting Instructions 21 Gas Line Ins...

Страница 4: ...THRU UNIT 41 062 PENINSULA UNIT 38 062 TOP VIEW 20 687 TOP VIEW 23 687 50 50 CORNER UNIT R H 38 062 REAR VIEW 16 125 36 125 16 125 21 687 15 50 36 062 29 75 SIDE VIEW END VIEW 32 625 31 875 UNIT DIMEN...

Страница 5: ...D VERTICAL MAX Horizontal Run With Required Vertical Run LEFT CORNER TOP VIEW LEFT CORNER TOP VIEW MAX 36 0 LOCATING YOUR APPLIANCE Horizontal Run With Min Vertical Run RIGHT BURNER SYSTEM LEFT BURNER...

Страница 6: ...oth sides of Fireplace for finishing material 3 The heat shield and rear standoff are equipped with nailing tabs Level Fireplace and nail or screw into place NOTE For Low Profile Enclosure Refer to Pa...

Страница 7: ...k and Glowing Ember installation refer to PAGE 16 FACING MATERIAL INSTALLATION Facing material Example DRYWALL may be installed flush with top of Fireplace Side facing to be installed to standoffs onl...

Страница 8: ...r Combustible Enclosure Top NOTE This UNIT is not Load Bearing MIN 36 0 FIGURE 1 FIGURE 2 SEE THROUGH FIREPLACE SHOWN FIREPLACE ASSEMBLY 1 Mount Door Cover Figure 2 First apply a small bead of High He...

Страница 9: ...FACING MATERIAL INSTALLATION Facing material Example DRYWALL may be installed Flush with top of Fireplace Side facing to be installed to standoffs only NOTE This UNIT is not Load Bearing Gyprock Gypro...

Страница 10: ...closure top Insulation sleeve must be installed so that it covers 7 0 flex pipe from fireplace up and to wall sleeve Refer to Page 11 for any additional information PENINSULA INSTALLATION INSTRUCTIONS...

Страница 11: ...9 FACING MATERIAL INSTALLATION Facing material Example DRYWALL may be installed Flush with top of Fireplace Side facing to be installed to standoffs only DRYWALL...

Страница 12: ...Warning Combustible objects must not be placed on a non com bustible mantle unless the non combustible mantle meets the mini mum height and width requirements for a combustible mantle Clearance to Com...

Страница 13: ...ND ADAPTER MINIMUM HEIGHT OF 52 0 MUST BE MAINTAINED FOR PROPER CLEARANCES INSULATION SLEEVE IS NOT REQUIRED THIS WILL LEAVE A 4 0 MINIMUM CLEARANCE TO COMBUSTIBLE TOP It is recommended for Propane Ho...

Страница 14: ...under water 12 Do not operate appliance unless completely installed as per installa tion instructions Operating and Maintenance Instructions This gas appliance should be installed by a qualified insta...

Страница 15: ...to bottom pan Refer to diagram for proper location Power cable to be routed through 6 x8 access hole 4 Connect power sensor and variable speed wall switch as shown in wiring diagram FAN KIT INSTALLATI...

Страница 16: ...ws in both ends To install slide the head into one of the teardrop slots then slide Grill to opposite side repeat procedure These screws may have to be adjusted for proper alinement and length 3 All G...

Страница 17: ...n each side as shown in illustration and install Brass Trim BAY WINDOW INSTRUCTIONS MDV38 SERIES CAUTION WARNING WHEN INSTALLING BAYWINDOW ASSEMBLY ORIGINAL GLASS WINDOW MUST REMAIN INSTALLED ON FIREP...

Страница 18: ...avoid plugging them Any fine dust found in bottom of bag is not to be used 2 To apply Glowing Embers tear embers into pieces and place along perimeter Burners as well as on top of Crushed Rock in Grat...

Страница 19: ...perimeter of the burner Do not place on middle burner as illus trated Care should be taken not to block burner ports Step 2 Take Log 4 and place onto burner using the two log tabs located on burner pa...

Страница 20: ...5 rests on the shape of Log 4 Log Pin Step 5 Place Log 3 onto both Log 1 and Log 5 using the log pins as a guide Log Pin Step 6 Place Log 2 onto both Log 1 and 4 using the log pins as a guide Ensure...

Страница 21: ...nit holding metal panel to firebox bottom remove the 2 screws and discard 2 Hold metal panel by the bottom and pull forward and down at the same time This will release the panel from the holder at the...

Страница 22: ...eways as this may damage Venturi FIGURE 2 4 To replace reverse procedure VALVE REMOVALAND REPLACEMENT 1 To remove Valve first follow Burner instructions 2 Remove GAS line and Deflector Pan 3 To remove...

Страница 23: ...er clockwise to ON 7 All models are supplied with a wall switch that turns the main burner on or off If main burner does not light immediately when you turn the gas control valve to ON ensure that the...

Страница 24: ...t 3 When using copper or flex connector use only approved fittings Always pro vide a union so that gas line can be easily disconnected for burner or fan servic ing See gas specification for pressure d...

Страница 25: ...the edge of terminal plate add 6 3 4 to clearances to arrive at center line NOTE Local Codes or Regulations may require different clearances Termination It is imperative that the vent termination be...

Страница 26: ...section allowed 3 Vent table has been established for 90 horizontal vertical runs With use of flex pipe distance not having 90 bends will not fall into vent table standards See Fig B Venting Table Fro...

Страница 27: ...ofile enclosure 2 5 rise per ft for horizontal runs with min vertical from Fireplace For installations other than Low Profile Enclosures top of horizontal with no sleeve requires a 2 5 clearance and 4...

Страница 28: ...sulation Shield must be installed where the vent passes from a lower living space into an attic space where the chimney is not enclosed It is designed to keep insulation materials away from the chimne...

Страница 29: ...protrudes approxi mately 2 to 3 inches past the 7 flex See Fig 1 Attach the 4 pipe to the termination first and secure with sealant and 4 screws washers then attach the 7 flex to the termination with...

Страница 30: ...305 1000 306 1000 306 3800 312 3800 132 3800 134 3800 302 3600 301 5000 P025WS 1000 150GE RED 1000 150MP BLACK 1000 218 Z1MT 3800 128 EMBER I EMBER R ZIRC 3800 255 3800 252 3800 173 3800 171 3800 172...

Страница 31: ...000 P136WR 1001 P129SI 1000 085 1000 214 1000 215 2000 080 2000 081 1001 P606SI NG 1001 P605SI LP Pilot Orifice LP 1001 P157SI Pilot Orifice NG 1001 P159SI MDV38 1000 255 NG 30 MDV38 1000 255 LP 50 MD...

Страница 32: ...30 ZDV48GP ZDV7SC ZDV4SS ZDVRS ZDV7FCL ZDVWT ZDVSS ZDVST ZDV7FC ZDV4FC ZDVAIS ZDVFS ZDVAAF ZDVAF2 ZDVAF3 ZDVFK5 ZDVFK8 ZDVFK20 FDVHT FDVVT30...

Страница 33: ...iple Burner Up to Three Viewing Areas Milli Volt Sit Valve Featuring less than 30 Sec Shut Down with Hi Lo Adjustment Wall Mount On Off Switch Ember Ash One Large Panel of Tempered Glass Four and Seve...

Страница 34: ...129 SIT unified 1001 P157SI Orifice Pilot LP 977 157 SIT 1001 P159SI Orifice Pilot NG 977 159 SIT 1001 P508SI HT Cable 16 1001 P633SI Valve Nova LP Hi Lo 0820633 1001 P634SI Valve Nova NG Hi Lo 082063...

Страница 35: ...rminals at wall switch If burner comes on replace defective Switch ON wall switch If okay jumper wires across wall switch wires at valve If burner comes on wires are faulty or connections are bad Gene...

Страница 36: ...service or maintenance h damage repairs inoperation or inefficiency resulting from faulty installation or application i electricity or fuel costs or any increase in electricity or fuel cost whatsoeve...

Отзывы: