The appliance can be fitted onto and inset into outside walls where the terminal 
does fall into any of the prohibited positions mentioned in the next section. The 
centre of the glass window is 157mm below the centre of the flue terminal. The 
centre  of the terminal should  be positioned at least 700mm above floor  level to 
allow space for the fascia to drop down on its runners. If the fireplace has to be 
altered a lintel will be required to support masonry over the opening and if it is 
to  be  surface  mounted  the  maximum  wall  thickness  allowed  is  405mm.  If  the 
appliance  is  to  be  inset  into  the  wall  this  may  be  increased  to  525mm.  If 
required,  a  longer  flue  duct  is  available  which  allows  the  maximum  wall 
thicknesses  to  be  increased  to  800mm  for  the  surface  mount  installation  and 
920mm for the inset installation. 

Flue Terminal Position

 

 

The minimum distances permissible from the flue terminal to obstructions and 
ventilation openings are shown below. 

 

 

 

 

 

 

 

DIMENSION 

TERMINAL POSITION 

MINIMUM 

DISTANCE 

Directly below an opening, air brick or window, etc. 

300mm 

Above an opening, air brick, opening windows, etc. 

300mm 

Horizontally to an opening, air brick, opening windows, 

etc. 

300mm 

Below plastic gutters, soil pipes or drain pipes 

300mm 

Below eaves 

300mm 

Below balconies or car port roof. 

600mm 

From a vertical drainpipe or soil pipe.     (Eire only 75) 

(GB) 300mm 

From an internal or external corner. 

600mm 

Above ground, roof or balcony level. 

300mm 

From a surface facing the terminal. 

600mm 

From a terminal facing a terminal. 

600mm 

From an opening in a carport (e.g. door, window) into the 

dwelling. 

1200mm 

Vertically from a terminal on the same wall. 

1500mm 

Horizontally from a terminal on the same wall. 

300mm 

Not shown  From an opening in a building directly opposite. 

600mm 

Figure 1 

Содержание KBFP00RN

Страница 1: ...Heater MODEL NUMBER KBFP00RN INSTALLATION USER AND SERVICING INSTRUCTIONS THESE INSTRUCTIONS MUST REMAIN WITH THE USER This appliance is suitable for use on Natural Gas G20 at a supply pressure of 20...

Страница 2: ...s is not a Do it yourself product and it must be installed by a competent person 2 The Installation Instructions must be adhered to without exception 3 The heat from this appliance will cause the wall...

Страница 3: ...a Panel b Decorative trim and 4 magnets if ordered Inset Installations only a Wall plate must be used for Inset Installations APPLIANCE DATA KBFP00RN GAS TYPE NATURAL GAS SUPPLY PRESSURE 20 mbar HEAT...

Страница 4: ...r the inset installation 3 Flue Terminal Position The minimum distances permissible from the flue terminal to obstructions and ventilation openings are shown below DIMENSION TERMINAL POSITION MINIMUM...

Страница 5: ...gh the whole base of the builders opening fireplace recess or beneath the flue box b Project at least 275mm in front of the glass window panel c Project at least 150mm beyond each side of the edge of...

Страница 6: ...s with the approval of the designers of the dwelling Fitting This appliance can be installed either by being fixed directly on to the surface or it can be inset into the inner leaf of a cavity wall Be...

Страница 7: ...flue connection on the back of the heat exchanger Note that the two flue tubes are not concentric and that the inner tube is positioned towards the top of the outer tube Using a 3 5mm diameter drill...

Страница 8: ...inner holes as shown in Figure 4 4 Temporally screw the convector box to the inner wall plate with four M5 screws Place the convector box over the protruding flue pipe and push the box into the hole...

Страница 9: ...ox flange Fix the heat exchanger through the convector box flanges to the inner fascia using the M5 bolts supplied Replace the self tapping screws that secure the flue to the wall plate Seal the flue...

Страница 10: ...panel slides up and down freely and locks in the top position COMMISSIONING 1 Before attempting to light the appliance the gas supply must be turned on by removing the cap from the isolator fitting a...

Страница 11: ...s from your fire we recommend that it be serviced annually 7 These instructions are provided to assist you to operate the fire correctly and should be kept in a safe place 8 If you have any reason to...

Страница 12: ...ger period d Depress control knob A slightly and turn anti clockwise to the ON position The main burner will not operate until this is done The main burner may light depending on the position of Contr...

Страница 13: ...the DOWN button on the handset Release when the flame is at the desired height or has gone out Once again the electric motor should be heard moving Control Knob B Cleaning the fire Ensure that the app...

Страница 14: ...wed of not smoking eating or drinking in the work area and that hands are washed before eating or drinking The appliance should be serviced at least once a year by a registered engineer and must inclu...

Страница 15: ...After cleaning the glass door inside and out replace it and secure with the eight nuts Tighten the nuts evenly Stubborn marks can be removed with steel wool and detergent AFTER REFITTING THE APPLIANCE...

Страница 16: ...he event of a part requiring replacement the parts list is as follows Part Description Part Number Motorised valve CV 104103 Remote hand control Receiver CV 104413 Pilot Burner NG Model CV 104506 Inje...

Страница 17: ...17 B 124830 Issue 2 BFM Europe Limited Trentham Lakes Stoke on Trent Staffordshire ST4 4TJ Tel 01782 339000 Fax 01782 339009 Email info bfm europe com www bfm europe com...

Отзывы: