PNEUMATIC LEVEL CONTROLLER
PNEUMATIC LEVEL CONTROLLER
MODEL: GEN 3
Installation, Operation & Maintenance Guide
MODEL: GEN 3
Installation, Operation & Maintenance Guide
www.kimray.com
6
Kimray reserves the right to modify or improve the designs or specifications of such products at anytime without notice.
Installation
NOTE:
Always check fastener tightness prior to installation,
testing, and use, as fasteners have the potential to
loosen in transit. This is recommended to ensure your
safety and proper function of the unit.
*Kimray assembly torque method below*
Four Bolt
Four Bolt
11
22
33
44
Three Bolt
Three Bolt
22
33
11
Install Onto Vessel
WARNING:
Before beginning installation, Block & Bleed valve.
Make sure all pressure is released from vessel, and
confirm no pressure remains in supply gas/instrument
air lines. Do not install in a location where Max Allowable
Working Pressure could be exceeded. Read and follow
instructions.
NPT Connection: Apply PTFE tape or pipe compound
to the male threads of the threaded mount. Tighten
sufficiently to seal the threads using a wrench on the flats
of the mounting piece.
Do not use a wrench on the aluminum enclosure/cover
to tighten the connection. Make sure the enclosure is
aligned vertically with the pilot on top when finished.
Flanged Connection: Use a suitable gasket between the
mount and the vessel connection flange.
NOTE:
When a Seat Gasket is disturbed during disassembly a
new Gasket should be installed during re-assembly to
ensure proper sealing.