This manual
is f
or
use b
y qualified personnel
onl
y
51
2022
JUNE 2022 / Rev: 1.0
For information about operating the Sol-Ark Hybrid inverter, see the SOl-Ark Owner’s Guide .
9. Connect Batteries (Sol-Ark should be POWERED “OFF”)
a. Connect the batteries to the Sol-Ark 12K.
b. Install included ferrites on the battery input cables. Slide the ferrite over the
battery cables so that both cables are within the toroid (as
shown Below).
c. When connecting batteries make sure the built-in battery disconnect is in the off
position while the batteries are connected, or arcing will occur.
d. Multi-system installs:
i. All systems in parallel are connected to the same battery bank, with each system
having its own battery cables to connect to the same large battery bank. Do not
use separate battery banks for parallel systems.
WARNING
RISK OF FIRE,ELECTRIC SHOCK, EXPLOSION, AND ARC FLASH
Do NOT reverse polarity of batteries! Damage will occur!
Failure to follow these instructions can result in equipment damage
9.2 Making DC Connections
NOTE
Note:
When making the connections, be sure to observe correct hard-
ware stacking and proper polarity, and ensure that nothing obstructs the
connection between the terminal surface and the battery cable lug,
Note:
Before connecting the DC cables from the SolArk Hybrid
Inverter to the battery, perform the procedures in "Making AC
Connections"