Device
Setting
Under 40A
Charger
40-60A
Charger
60-150A
Charger
Charge
Controller
Absorb Time
Under 6 min
Under 4 min
Under 2 min
Absorb Voltage
56 V
Battery Capacity
150 Ah (7.5 kWh) per HAB™
Battery Temperature
Compensation
Do not use an external battery temperature sensor with these
batteries. If the sensor is required for a charge controller or
inverter charger to work, set the battery temperature compensa-
tion to 0mV / °C.
Battery Type
Lithium Ion or Custom - whichever provides access to all the
required settings
Battery Voltage
48 V
Bulk Voltage
56 V
Charge Cycle
3 Stage
Equalization
Disabled
Max Float Current
10 A
Float Voltage
52.8 V
Maximum
Charge Rate
1C
Recharge / Re-bulk
Volts
Set to start charging from solar before charging by AC (just
above the inverter/charger’s recharge/re-bulk voltage of 51.4 V).
Battery
Monitor
Midpoint Sensor
If you are using a battery monitor with midpoint sensors, secure
the midpoint sensor leads out of the way and electrically isolate
the midpoint sensors with electrical tape, shrink wrap, or any
other appropriate method.
Midpoint sensors are only used on strings of batteries in series.
Since the units are NEVER connected in series, midpoint sen-
sors are not used.
Battery Temperature
Sensor
Do not use an external battery temperature sensor with these
batteries.
Battery Temperature
Compensation
If the sensor is required for the battery monitor to work, set the
battery temperature compensation to 0mV / °C