P/N 03-0210-501-2000-01 • ISS 06MAY19 

EN: Installation Sheet 

Description 

The ZP885 Intelligent Addressable Manual Call Point is 
designed for indoor use and supports the Ziton ZP7 protocol. 

The device address and communication LED functionality (on 
or off) can be configured before or after installation (with or 
without power connected to the unit) using the ActivSense 
mobile application and RFID tool (see “Configuration” below for 
more details). 

All units are supplied with a resettable element – this can be 
replaced with a breakable element, if required (order numberN-
MC-BS). See “Replacing the resettable element” on page 3. 

Figures 

Figure 1: Backbox and mounting holes 

Figure 2: Front assembly terminal block 

Figure 3: Unlocking the front cover 

Figure 4: Removing the front cover 

Figure 5: Removing the resettable element 

Figure 6: Replacing the front cover 

Installation 

Caution: 

This product must be installed and maintained by 

qualified personnel adhering to all local or national installation 
requirements and any other applicable regulations. 

The manual call point can be surface mounted or recess 
mounted. 

• 

For surface mounting, order backbox N-MC-BB-R (red), N-
MC-BB-U (blue), N-MC-BB-G (green), N-MC-BB-W 
(white), or N-MC-BB-Y (yellow). 

• 

For recess mounting, order recess adaptor N-MC-AFM-R 
(red only). 

Remember to remove the protective dust cover before 
installation. 

Note: 

The dust cover may also be used to indicate when the 

unit is not operational (for example, before commissioning, 
during maintenance, when disabled, etc.) 

To surface mount the manual call point: 

1.  Fix the backbox onto the wall using 4 × M4 screws (not 

supplied) and feed the loop cable through the selected 
cable knockouts. 

See Figure 1 for the location of the mounting holes. 

2.  Connect loop cable to the supplied terminal block, and 

then plug the terminal block into the PCB connector on the 
back of the front assembly (see Figure 2). 

Use the supplied cable link to test cable continuity during 
installation. 

See “Wiring” below for terminal block connections and 
loop cable specifications. 

3.  Unlock and remove the front cover, and then remove the 

resettable element. 

To unlock the front cover, insert the key and turn it 
clockwise (two clicks), then pull the cover outwards from 
the bottom to remove it (see Figure 3 and Figure 4). 

To remove the resettable element, push the element up, 
and then pull it out (see Figure 5). 

4.  Fix the front assembly to the backbox using the 2 screws 

supplied with the unit (located in the backbox).  

5.  Replace the resettable element (or add the breakable 

element, if required), and then replace the front cover (see 
Figure 6). 

Turn the key anticlockwise (two clicks) to lock the cover, 
and then remove the key. 

Finally, set the device address (if you didn’t do this before 
installation) and test the manual call point (see “Addressing” 
below 
and “Testing” on page 3)

Wiring 

For optimal system performance use a 1.5 mm² (15 AWG) loop 
cable with a maximum length of 2.8 km. 

Wire the unit as described below. Observe the indicated 
polarity. 

 

Terminal 

Description 

+A 

Positive line (+) 

+B 

Positive line (+) 

–A 

Negative line (–) 

–B 

Negative line (–) 

Configuration 

Use the ActivSense mobile application and RFID tool to 
configure the device address and the communication LED 
functionality (on or off). These can be configured before or 
after installation (with or without power connected to the unit). 

Addressing 

Set the device address (the address range is 001-127). 

Status LEDs 

The device status is indicated by two colour changing LEDs on 
the front of the unit, as shown in the table below.  

Use the ActivSense mobile application and RFID tool to 
disable the communication LED, if required. 

 

State 

Indication 

Alarm  

Flashing red LEDs [1] 

Fault 

Flashing yellow LEDs 

Communicating 

Flashing green LEDs 

[1] This may also indicate an active Locate Device command from the 
control panel. 

Содержание ZP885

Страница 1: ...2019 UTC Fire Security All rights reserved 1 17 P N 03 0210 501 2000 01 ISS 06MAY19 ZP885 Intelligent Addressable Manual Call Point Installation Sheet EN ES FR NL PT SV TR 1 2 3 4 5 6...

Страница 2: ...terminal block into the PCB connector on the back of the front assembly see Figure 2 Use the supplied cable link to test cable continuity during installation See Wiring below for terminal block conne...

Страница 3: ...on This section provides a summary on the declared performance according to the Construction Products Regulation EU 305 2011 and Delegated Regulations EU 157 2014 and EU 574 2014 For detailed informat...

Страница 4: ...C BB R rojo N MC BB U azul N MC BB G verde N MC BB W blanco o N MC BB Y amarillo Para realizar un montaje empotrado pida el adaptador N MC AFM R solo en rojo No olvide retirar la cubierta protectora c...

Страница 5: ...eloj un clic Para restablecer el dispositivo gire la llave en sentido contrario a las agujas del reloj un clic Reinicie el panel de control despu s de la prueba Reemplazo del elemento reseteable Reemp...

Страница 6: ...INCLUYENDO CUALQUIER DISTRIBUIDOR O VENDEDOR AUTORIZADO CUENTE CON LA FORMACI N O EXPERIENCIA PERTINENTE PARA INSTALAR CORRECTAMENTE PRODUCTOS RELACIONADOS CON LA SEGURIDAD Para obtener m s informaci...

Страница 7: ...ez respecter la polarit Bornier Description A Ligne positive B Ligne positive A Ligne n gative B Ligne n gative Configuration Utilisez l application mobile ActivSense et l outil RFID pour configurer l...

Страница 8: ...if est conforme aux exigences essentielles et aux autres dispositions pertinentes de la directive 2014 53 UE 2012 19 UE directive DEEE au sein de l Union europ enne les produits portant ce symbole ne...

Страница 9: ...vervolgens van onder uit naar buiten om deze te verwijderen zie afbeelding 3 en afbeelding 4 Om het opnieuw instelbare element te verwijderen duwt u het element omhoog en trekt u het eruit zie afbeel...

Страница 10: ...an de aangegeven prestaties conform de Verordening Bouwproducten EU 305 2011 en Gedelegeerde Verordeningen EU 157 2014 en EU 574 2014 Zie de Prestatieverklaring van het product voor gedetailleerde inf...

Страница 11: ...e ser montada superf cie ou embutida Para montagem em superf cie encomende a base de montagem N MC BB R vermelho N MC BB U azul N MC BB G verde N MC BB W branco ou N MC BB Y amarelo Para montagem embu...

Страница 12: ...clique Para reiniciar o dispositivo gire a chave no sentido anti hor rio um clique Reponha o painel de controlo ap s o teste Substituir o elemento rearm vel Substitua o elemento rearm vel ou adicione...

Страница 13: ...cumenta o mais recente do produto visite firesecurityproducts com Avisos e isen es de responsabilidade dos produtos ESTES PRODUTOS DESTINAM SE A SER VENDIDOS E INSTALADOS POR PROFISSIONAIS QUALIFICADO...

Страница 14: ...dan 14 Kablar F r optimal systemprestanda anv nd en 1 5 mm 15 AWG slingkabel med en maximal l ngd p 2 8 km Anslut enheten enligt beskrivningen nedan Observera den angivna polariteten Pol Beskrivning A...

Страница 15: ...erensst mmer med de v sentliga kraven och andra relevanta best mmelser i direktivet 2014 53 EU 2012 19 EU WEEE direktivet Produkter som r markerade med denna symbol f r ej kasseras som osorterat hush...

Страница 16: ...d ar do ru ekin bkz ekil 5 4 niteyle birlikte temin edilen arka kutuda yer alan 2 viday kullanarak n tertibat arka kutuya sabitleyin 5 Resetlenebilir eyi de i tirin veya gerekiyorsa k r labilir eyi e...

Страница 17: ...C Fire Security B V Kelvinstraat 7 6003 DH Weert Hollanda lk CE i aretinin y l 2019 Performans Bildirimi numaras 1 03 0210 360 3000 EN 54 EN 54 11 Tip A Mekan Kullan m r n tan lama 1 ZP885 ZP885S06 ZP...

Отзывы: