7. Recommended Locations for Smoke Alarms

  

Locate smoke alarms in all sleeping areas. Try to monitor the exit path as the bedrooms are usually farthest 
from the exit. If more than one sleeping area exists, locate additional alarms in each sleeping area.

  

Locate additional alarms to monitor any stairway as stairways act like chimneys for smoke and heat.

  

Locate at least one alarm on every floor level.

  

Locate an alarm in every bedroom.

  

Locate an alarm in every room where electrical appliances are operated (i.e. portable heaters or humidifiers).

  

Locate an alarm in every room where someone sleeps with the door closed. The closed door may 
prevent an alarm not located in that room from waking the sleeper.

  

Smoke, heat, and combustion products rise to the ceiling and spread horizontally. Mounting the smoke 
alarm on the ceiling in the center of the room places it closest to all points in the room. Ceiling mounting 
is preferred in ordinary residential construction.

ANYWHERE ALONG 
THIS BOLD SURFACE

Locations permitted for smoke

alarms and smoke detectors

on tray-shaped ceilings.

(4")

10 cm

(4")

10 cm

(12")

30.5 cm

(12")

30.5 cm

(3')

0.9 m

(3')

0.9 m

(3')

0.9 m

ANYWHERE ALONG 
THIS BOLD SURFACE

Locations permitted for smoke

alarms and smoke detectors

on tray-shaped ceilings.

(4")

10 cm

(4")

10 cm

(12")

30.5 cm

(12")

30.5 cm

(3')

0.9 m

(3')

0.9 m

(3')

0.9 m

ANYWHERE ALONG 
THIS BOLD SURFACE

Locations permitted for smoke

alarms and smoke detectors

on tray-shaped ceilings.

(4")

10 cm

(4")

10 cm

(12")

30.5 cm

(12")

30.5 cm

(3')

0.9 m

(3')

0.9 m

(3')

0.9 m

ANYWHERE ALONG 
THIS BOLD SURFACE

Locations permitted for smoke

alarms and smoke detectors

on tray-shaped ceilings.

(4")

10 cm

(4")

10 cm

(12")

30.5 cm

(12")

30.5 cm

(3')

0.9 m

(3')

0.9 m

(3')

0.9 m

ANYWHERE ALONG 
THIS BOLD SURFACE

Locations permitted for smoke

alarms and smoke detectors

on tray-shaped ceilings.

(4")

10 cm

(4")

10 cm

(12")

30.5 cm

(12")

30.5 cm

(3')

0.9 m

(3')

0.9 m

(3')

0.9 m

ANYWHERE ALONG 
THIS BOLD SURFACE

Locations permitted for smoke

alarms and smoke detectors

on tray-shaped ceilings.

(4")

10 cm

(4")

10 cm

(12")

30.5 cm

(12")

30.5 cm

(3')

0.9 m

(3')

0.9 m

(3')

0.9 m

NFPA 72 states: “Smoke alarms in rooms with 
ceiling slopes greater than 0.3 m in 2.4 m (1 ft in 8 ft) 
horizontally shall be located on the high side of the 
room.” NFPA 72 states: “A row of detectors shall be 
spaced and located within 0.9 m (3 ft) of the peak of 
the ceiling measured horizontally.”

Figure 7-A

Figure 7-B

Figure 7-C

Содержание P4010ACS-WCA

Страница 1: ...0ACS WCA Model P4010LACS WCA Safety Light WireLESS Interconnect You do NOT need a home wi fi system to use these units Multiple wireless units create their own independent wireless alarm network 120 V...

Страница 2: ...ould never play with the unit Your Kidde Smoke Alarm was designed for use in a residential environment It is not designed for use in a recreational vehicle RV or boat Note Please take a few minutes to...

Страница 3: ...cations For Smoke Alarms 10 8 Locations To Avoid 12 9 Activation And Wireless Alarm Network 12 9 1 Setting Up A Wireless Alarm Network 13 9 2 Adding Another Device to an Existing Wireless Alarm Networ...

Страница 4: ...If the inside of the door is cool place your shoulder against it open it slightly and be ready to slam it shut if heat and smoke rush in If the escape route requires you to go through smoke stay clos...

Страница 5: ...of Carbon Monoxide CO at high concentrations which can kill you 1 Immediately move to fresh air outdoors or by an open door window Do a head count to check that all persons are accounted for Do not r...

Страница 6: ...0 sec After button push Smoke previously detected only on the initiating alarm unit Push test button to clear Alarm Memory NOTE standard test sequence will follow Push release button again to cancel t...

Страница 7: ...of Unit Life Hush Mode after push release Test Hush button during End of Life Voice Temporarily Silenced End of Unit Life chirps silenced for 24 hrs 7 days after End of Unit Life chirps begin the chi...

Страница 8: ...10 year battery and unit life Product Features and Specifications Temperature Operating Range 4 4 C 40 F to 37 8 C 100 F Humidity Operating range up to 95 RH non condensing Audible Alarm 85 dB at 10...

Страница 9: ...nsing alarms may detect invisible fire particles associated with fast flaming fires sooner than photoelectric alarms Photoelectric sensing alarms may detect visible fire particles associated with slow...

Страница 10: ...smoke alarms and smoke detectors on tray shaped ceilings 4 10cm 4 10cm 12 30 5cm 12 30 5cm ANYWHERE ALONG THIS BOLD SURFACE Locations permitted for smoke alarms and smoke detectors on tray shaped cei...

Страница 11: ...MA 02269 Mobile Home Installation Modern mobile homes have been designed and built to be energy efficient Install smoke alarms as recommended on the previous page In older mobile homes that are not w...

Страница 12: ...condensing Moisture or steam can cause nuisance alarms In insect infested areas Smokealarmsshouldnotbeinstalledwithin0 9m 3ft ofthedoortoabathroomcontainingatuborshower forced air supply ducts used fo...

Страница 13: ...position on ALL devices using the white tool included with the Quick Start Guide Once powered the light rings will glow red and voice message will announce Ready to connect Follow Quick Start instruct...

Страница 14: ...beeps Release button Sonar ping will stop Device will announce that setup is complete and the number of connected devices G Setup complete If all devices flash green and Sonar ping has stopped the de...

Страница 15: ...ress and hold the button on ONE INSTALLED device on your network until you hear two beeps Release button You will hear Searching for other devices Light will pulse green and device will sound a contin...

Страница 16: ...ettings b Conclude reset Light ring will flash green once and then it will pulse red You will hear the words Ready to connect follow quick start instructions Device has been reset See Section 9 1 to b...

Страница 17: ...combination alarm and detector guard have been evaluated and found suitable for that purpose WARNING The alarm cannot be operated from power derived from a square wave modified square wave or modified...

Страница 18: ...e to the alarm failure to operate or a shock hazard Makecertainalarmsarewiredtoacontinuous non switched powerline NOTE Use standard CSA Listed household wire as required by local codes available at al...

Страница 19: ...the following three steps Plug the AC QUICK CONNECTOR into the wiring harness attached to the unit making sure that the locks on the connector snap into place Then push the excess wire back into the...

Страница 20: ...larm interconnect capability When one hardwire or wireless interconnect unit sounds an alarm all other compatible hardwire or wireless interconnected units will also alarm This model is not designed t...

Страница 21: ...cuitry horn speaker and battery are working If the alarm or voice does not sound or gives erratic or low volume sound the unit must be replaced See Permanently Disable Alarm Discharge Battery section...

Страница 22: ...at night Moving the unit to a different location might allow the unit to determine a valid Night Day cycle WARNING REPLACE UNIT AS SOON AS POSSIBLE WHEN IN END OF UNIT LIFE OR LOW BATTERY MODE 12 Rec...

Страница 23: ...nd during alarm Depending on unit locations and the location of the source of smoke it is possible to have more than one initiating unit If you suspect a nuisance alarm situation you can use this feat...

Страница 24: ...idity or temperatures may reduce battery life WARNING NO SERVICEABLE PARTS INCLUDED DO NOT ATTEMPT TO OPEN THE ALARM FOR ANY REASON Do not try to repair the alarm yourself Low Battery This alarm is eq...

Страница 25: ...onger function Oncethealarmbatteryhasbeendischarged thealarmcannotbemountedontothemountingplate orreactivated To Permanently Disable Alarm Discharge Battery Rotate the alarm counterclockwise to remove...

Страница 26: ...damage the alarm If the alarm is in Fault mode and the Red LED is blinking a fault code of 10 or 14 flashes after a Test Hush button push the alarm may be in need of cleaning After cleaning press the...

Страница 27: ...chain ladder Have a family meeting and discuss your escape plan showing everyone what to do in case of fire and where to meet after they leave the house Ensure that small children hear the alarm and...

Страница 28: ...le The required number of smoke alarms might not provide reliable early warning protection for those areas separated by a door from the areas protected by the required smoke alarms For this reason it...

Страница 29: ...each separate dwelling unit sleeping area within 6 4 m 21 of any door to a sleeping room with the distance measured along a path of travel 3 On every level of a dwelling unit including basements 4 On...

Страница 30: ...is product or for any indirect special incidental or consequential damages or costs or expenses incurred by the consumer or any other user of this product whether due to a breach of contract negligenc...

Отзывы: