WARNING! BATTERY DOOR WILL NOT CLOSE UNLESS A 
BATTERY IS PRESENT. REMOVAL OF THE SMOKE ALARM 
BATTERY AND DISCONNECTING OR LOSS OF AC POWER 
WILL RENDER THE SMOKE ALARM INOPERATIVE.

ELECTRICAL RATING: 120 VAC, 60HZ, 80mA maximum per alarm 
(maximum 80mA for originating unit with 24 devices interconnected).

CONTENTS OF THIS MANUAL

1 -- RECOMMENDED LOCATIONS FOR SMOKE ALARMS

2 -- LOCATIONS TO AVOID

3 -- INSTALLATION INSTRUCTIONS

4 -- OPERATION AND TESTING

5 -- NUISANCE ALARMS

6 -- MAINTENANCE

7 -- LIMITATIONS OF SMOKE ALARMS

8 -- GOOD SAFETY HABITS

9 -- NFPA PROTECTION STANDARD 72

10 -- CALIFORNIA STATE FIRE MARSHAL REQUIRED INFORMATION

11 -- SERVICE AND WARRANTY

1. RECOMMENDED LOCATIONS FOR ALARMS

•  Locate the first alarm in the immediate area of the bedrooms.  

Try to monitor the exit path as the bedrooms are usually farthest 
from the exit.  If more than one sleeping area exists, locate addi-
tional alarms in each sleeping area.

•  Locate additional alarms to monitor any stairway as stairways act 

like chimneys for smoke and heat.

•  Locate at least one alarm on every floor level.

•  Locate an alarm in every bedroom.

•  Locate an alarm in every room where electrical appliances are 

operated (i.e. portable heaters or humidifiers).

•  Locate an alarm in every room where someone sleeps with the 

door closed. The closed door may prevent an alarm not located 
in that room from waking the sleeper.

•  Smoke, heat, and combustion products rise to the ceiling and 

spread horizontally.  Mounting the smoke alarm on the ceiling in 
the center of the room places it closest to all points in the room.  
Ceiling mounting is preferred in ordinary residential construction. 

•  For mobile home installation, select locations carefully to avoid 

1375-7213-00(21008164-EN A).indd   2

1375-7213-00(21008164-EN A).indd   2

2010.10.7   2:06:23 PM

2010.10.7   2:06:23 PM

Содержание P12040

Страница 1: ...u expect nothing less when the lives of your family are at stake Kidde alarms and accessories CAN ONLY BE interconnected with other Kidde alarms and accessories as well as specified brands and models...

Страница 2: ...thest from the exit If more than one sleeping area exists locate addi tional alarms in each sleeping area Locate additional alarms to monitor any stairway as stairways act like chimneys for smoke and...

Страница 3: ...d peaked or cathedral ceilings at or within 3 ft 0 9m of the highest point measured hori zontally NFPA 72 states Smoke alarms in rooms with ceiling slopes greater than 1 ft in 8 ft 3m in 2 4m horizont...

Страница 4: ...USE 2 LOCATIONS TO AVOID In the garage Products of combustion are present when you start your automobile Less than 4 10cm from the peak of an A frame type ceiling In an area where the temperature may...

Страница 5: ...nverters These types of inverters are sometimes used to supply power to the structure in off grid installations such as solar or wind derived power sources These power sources produce high peak voltag...

Страница 6: ...ndard UL listed household wire as required by local codes available at all electrical supply stores and most hardware stores FIGURE 4 INTERCONNECT WIRING DIAGRAM WIRES ON ALARM HARNESS CONNECTED TO Bl...

Страница 7: ...e that the mounting screws are positioned in the small ends of the keyholes before tightening the screws see figure 5 5 Plug the AC QUICK CONNECTOR into the back of the alarm see figure 6 making sure...

Страница 8: ...H CONTROL The HUSH feature has the capability of temporarily desensitizing the alarm circuit for approximately 10 minutes This feature is to be used only when a known alarm condition such as smoke fro...

Страница 9: ...m which senses the smoke or is being tested the originating unit will flash rapidly All other units in the interconnect system will sound an alarm but their red LED s will NOT flash rapidly The green...

Страница 10: ...sance alarms For more information refer to section 4 OPERATION AND TESTING 6 MAINTENANCE IF TAMPER RESIST PIN HAS BEEN USED REFER TO TAMPER RESIST LOCKING PIN IN SECTION 3 FOR PIN REMOVAL INSTRUCTIONS...

Страница 11: ...ADY 1222 GOLD PEAK 1604P OR 1604S Alkaline Type ENERGIZER 522 DURACELL MN1604 MX1604 GOLD PEAK 1604A PANASONIC 6AM6 6AM 6 6AM 6PI 6AM6X and 6LR61 GA Lithium Type ULTRALIFE U9VL J NOTE WEEKLY TESTING I...

Страница 12: ...are often unpredictable For maximum protection Kidde recom mends that both Ionization and Photoelectric alarms be installed A battery powered alarm must have a battery of the specified type in good c...

Страница 13: ...l occupants to test your plan before an emergency You may not be able to reach your chil dren It is important they know what to do Current studies have shown smoke alarms may not awaken all sleeping i...

Страница 14: ...in existing one and two family dwelling units 2 Outside of each separate sleeping area in immediate vicinity of the sleeping rooms 3 On each level of the dwelling unit includ ing basements Exception I...

Страница 15: ...smoke alarm installed in each separate sleeping area in the vicinity of but outside of the bedrooms and heat or smoke alarms in the living rooms dining rooms bedrooms kitch ens hallways attics furnace...

Страница 16: ...ANY CASE EXCEED THE COST OF REPLACEMENT OF SMOKE ALARM AND IN NO CASE SHALL KIDDE OR ANY OF ITS PARENT OR SUBSIDIARY CORPORATIONS BE LIABLE FOR CONSEQUENTIAL LOSS OR DAMAGES RESULTING FROM THE FAILUR...

Отзывы: