3. INSTALLATION  INSTRUCTIONS

WIRING REQUIREMENTS

•  This smoke alarm should be installed on a U.L. listed or recognized 

junction box. All connections should be made by a qualified elec-
trician and all wiring used shall be in accordance with articles 210 
and 300.3(B) of the U.S. National Electrical Code ANSI/NFPA 70, 
NFPA 72 and/or any other codes having jurisdiction in your area. 
The multiple station interconnect wiring to the alarms must be run 
in the same raceway or cable as the AC power wiring.  In addition, 
the resistance of the interconnect wiring shall be a maximum  of 
10 ohms.

•  The appropriate power source is 120 Volt AC Single Phase sup-

plied from a non-switchable circuit which is not protected by a 
ground fault interrupter.

•  WARNING: This alarm cannot be operated from power derived 

from a square wave, modified square wave or modified sine wave 
inverters. These types of inverters are sometimes used to supply 
power to the structure in off grid installations, such as solar or 
wind derived power sources. These power sources produce high 
peak voltages that will damage the alarm.

WIRING INSTRUCTIONS FOR AC QUICK CONNECT HARNESS

CAUTION! TURN OFF THE MAIN POWER TO THE CIRCUIT 
BEFORE WIRING THE ALARM.

•  For alarms that are used as single station, DO NOT CONNECT THE 

RED WIRE TO ANYTHING. Leave the red wire insulating cap in 
place to make certain that the red wire cannot contact any metal 
parts or the electrical box.

•  When alarms are interconnected, all interconnected units must be 

powered from a single circuit.

•  A maximum of 24 Kidde devices may be interconnected in a mul-

tiple station arrangement.  The interconnect system should not 
exceed the NFPA interconnect limit of 12 smoke alarms and/or 18 
alarms total (smoke, heat, carbon monoxide, etc.). With 18 alarms 
interconnected, it is still possible to interconnect up to a total of 6 
remote signaling devices and/or relay modules.

1375-7213-00(21008164-EN A).indd   5

1375-7213-00(21008164-EN A).indd   5

2010.10.7   2:06:24 PM

2010.10.7   2:06:24 PM

Содержание P12040

Страница 1: ...u expect nothing less when the lives of your family are at stake Kidde alarms and accessories CAN ONLY BE interconnected with other Kidde alarms and accessories as well as specified brands and models...

Страница 2: ...thest from the exit If more than one sleeping area exists locate addi tional alarms in each sleeping area Locate additional alarms to monitor any stairway as stairways act like chimneys for smoke and...

Страница 3: ...d peaked or cathedral ceilings at or within 3 ft 0 9m of the highest point measured hori zontally NFPA 72 states Smoke alarms in rooms with ceiling slopes greater than 1 ft in 8 ft 3m in 2 4m horizont...

Страница 4: ...USE 2 LOCATIONS TO AVOID In the garage Products of combustion are present when you start your automobile Less than 4 10cm from the peak of an A frame type ceiling In an area where the temperature may...

Страница 5: ...nverters These types of inverters are sometimes used to supply power to the structure in off grid installations such as solar or wind derived power sources These power sources produce high peak voltag...

Страница 6: ...ndard UL listed household wire as required by local codes available at all electrical supply stores and most hardware stores FIGURE 4 INTERCONNECT WIRING DIAGRAM WIRES ON ALARM HARNESS CONNECTED TO Bl...

Страница 7: ...e that the mounting screws are positioned in the small ends of the keyholes before tightening the screws see figure 5 5 Plug the AC QUICK CONNECTOR into the back of the alarm see figure 6 making sure...

Страница 8: ...H CONTROL The HUSH feature has the capability of temporarily desensitizing the alarm circuit for approximately 10 minutes This feature is to be used only when a known alarm condition such as smoke fro...

Страница 9: ...m which senses the smoke or is being tested the originating unit will flash rapidly All other units in the interconnect system will sound an alarm but their red LED s will NOT flash rapidly The green...

Страница 10: ...sance alarms For more information refer to section 4 OPERATION AND TESTING 6 MAINTENANCE IF TAMPER RESIST PIN HAS BEEN USED REFER TO TAMPER RESIST LOCKING PIN IN SECTION 3 FOR PIN REMOVAL INSTRUCTIONS...

Страница 11: ...ADY 1222 GOLD PEAK 1604P OR 1604S Alkaline Type ENERGIZER 522 DURACELL MN1604 MX1604 GOLD PEAK 1604A PANASONIC 6AM6 6AM 6 6AM 6PI 6AM6X and 6LR61 GA Lithium Type ULTRALIFE U9VL J NOTE WEEKLY TESTING I...

Страница 12: ...are often unpredictable For maximum protection Kidde recom mends that both Ionization and Photoelectric alarms be installed A battery powered alarm must have a battery of the specified type in good c...

Страница 13: ...l occupants to test your plan before an emergency You may not be able to reach your chil dren It is important they know what to do Current studies have shown smoke alarms may not awaken all sleeping i...

Страница 14: ...in existing one and two family dwelling units 2 Outside of each separate sleeping area in immediate vicinity of the sleeping rooms 3 On each level of the dwelling unit includ ing basements Exception I...

Страница 15: ...smoke alarm installed in each separate sleeping area in the vicinity of but outside of the bedrooms and heat or smoke alarms in the living rooms dining rooms bedrooms kitch ens hallways attics furnace...

Страница 16: ...ANY CASE EXCEED THE COST OF REPLACEMENT OF SMOKE ALARM AND IN NO CASE SHALL KIDDE OR ANY OF ITS PARENT OR SUBSIDIARY CORPORATIONS BE LIABLE FOR CONSEQUENTIAL LOSS OR DAMAGES RESULTING FROM THE FAILUR...

Отзывы: