•  When mixing models which have battery backup (i12040, i12040A, 

i12060, i12060A, i12080, i12080A, i12090A, i4618, i1418A, 1275, 
1276, 1285, 1296, PE120, P12040, PI2000, PI2010, KN-COSM-
IB, RF-SM-ACDC, KN-COPE-I, KN-SMFM-I, HD135F, KN-COB-IC, 
KN-COP-IC) with models without battery backup, (i1235, i12020, 
i12020A, KN-COSM-I SM120X, CO120X, SL177I) be advised that 
the models without battery backup will not respond during an AC 
power failure.

•  The maximum wire run distance between the first and last unit in 

an interconnected system is 1000 feet.

•  Figure 4 illustrates interconnection wiring.  Improper connection 

will result in damage to the alarm, failure to operate, or a shock 
hazard.

•  Make certain alarms are wired to a continuous (non-switched) 

power line.  NOTE: Use standard UL listed household wire (as 
required by local codes) available at all electrical supply stores and 
most hardware stores.

FIGURE 4 INTERCONNECT WIRING DIAGRAM

WIRES ON ALARM HARNESS  CONNECTED TO

Black 

Hot Side of AC Line

White 

Neutral Side of AC Line

Red 

Interconnect Lines (Red Wires) of 

 

Other Units in the Multiple 

 

Station Set up

BATTERY INSTALLATION

See Maintenance (section 6) for battery installation

CAUTION! IF BATTERY REMINDER FINGER IS NOT HELD DOWN 
IN THE BATTERY COMPARTMENT BY THE BATTERY, THE 
BATTERY DOOR WILL NOT CLOSE, THE AC QUICK CONNECTOR 
WILL NOT ATTACH TO THE ALARM, AND THE ALARM WILL NOT 
ATTACH TO THE TRIM RING (SEE SECTION 6, FIGURE 9).

FUSE OR CIRCUIT BREAKER 

RED 

BLACK 

WHITE 

BLACK 

WHITE 

RED 

CONNECTOR 

CONNECTOR 

Kidde 

Relay Module 

SM120X 

First 
Alarm 

Additional 
Alarm 

Optional 

Accessory 

Additional 
Alarm 

1375-7213-00(21008164-EN A).indd   6

1375-7213-00(21008164-EN A).indd   6

2010.10.7   2:06:24 PM

2010.10.7   2:06:24 PM

Содержание P12040

Страница 1: ...u expect nothing less when the lives of your family are at stake Kidde alarms and accessories CAN ONLY BE interconnected with other Kidde alarms and accessories as well as specified brands and models...

Страница 2: ...thest from the exit If more than one sleeping area exists locate addi tional alarms in each sleeping area Locate additional alarms to monitor any stairway as stairways act like chimneys for smoke and...

Страница 3: ...d peaked or cathedral ceilings at or within 3 ft 0 9m of the highest point measured hori zontally NFPA 72 states Smoke alarms in rooms with ceiling slopes greater than 1 ft in 8 ft 3m in 2 4m horizont...

Страница 4: ...USE 2 LOCATIONS TO AVOID In the garage Products of combustion are present when you start your automobile Less than 4 10cm from the peak of an A frame type ceiling In an area where the temperature may...

Страница 5: ...nverters These types of inverters are sometimes used to supply power to the structure in off grid installations such as solar or wind derived power sources These power sources produce high peak voltag...

Страница 6: ...ndard UL listed household wire as required by local codes available at all electrical supply stores and most hardware stores FIGURE 4 INTERCONNECT WIRING DIAGRAM WIRES ON ALARM HARNESS CONNECTED TO Bl...

Страница 7: ...e that the mounting screws are positioned in the small ends of the keyholes before tightening the screws see figure 5 5 Plug the AC QUICK CONNECTOR into the back of the alarm see figure 6 making sure...

Страница 8: ...H CONTROL The HUSH feature has the capability of temporarily desensitizing the alarm circuit for approximately 10 minutes This feature is to be used only when a known alarm condition such as smoke fro...

Страница 9: ...m which senses the smoke or is being tested the originating unit will flash rapidly All other units in the interconnect system will sound an alarm but their red LED s will NOT flash rapidly The green...

Страница 10: ...sance alarms For more information refer to section 4 OPERATION AND TESTING 6 MAINTENANCE IF TAMPER RESIST PIN HAS BEEN USED REFER TO TAMPER RESIST LOCKING PIN IN SECTION 3 FOR PIN REMOVAL INSTRUCTIONS...

Страница 11: ...ADY 1222 GOLD PEAK 1604P OR 1604S Alkaline Type ENERGIZER 522 DURACELL MN1604 MX1604 GOLD PEAK 1604A PANASONIC 6AM6 6AM 6 6AM 6PI 6AM6X and 6LR61 GA Lithium Type ULTRALIFE U9VL J NOTE WEEKLY TESTING I...

Страница 12: ...are often unpredictable For maximum protection Kidde recom mends that both Ionization and Photoelectric alarms be installed A battery powered alarm must have a battery of the specified type in good c...

Страница 13: ...l occupants to test your plan before an emergency You may not be able to reach your chil dren It is important they know what to do Current studies have shown smoke alarms may not awaken all sleeping i...

Страница 14: ...in existing one and two family dwelling units 2 Outside of each separate sleeping area in immediate vicinity of the sleeping rooms 3 On each level of the dwelling unit includ ing basements Exception I...

Страница 15: ...smoke alarm installed in each separate sleeping area in the vicinity of but outside of the bedrooms and heat or smoke alarms in the living rooms dining rooms bedrooms kitch ens hallways attics furnace...

Страница 16: ...ANY CASE EXCEED THE COST OF REPLACEMENT OF SMOKE ALARM AND IN NO CASE SHALL KIDDE OR ANY OF ITS PARENT OR SUBSIDIARY CORPORATIONS BE LIABLE FOR CONSEQUENTIAL LOSS OR DAMAGES RESULTING FROM THE FAILUR...

Отзывы: