![Kidde 23911-K086 Скачать руководство пользователя страница 7](http://html1.mh-extra.com/html/kidde/23911-k086/23911-k086_operation-and-maintenance-manual_1965001007.webp)
TM206
7 of 35
Issue 1.0
4 Technical
specification
Table 1 - Electrical specifications
ITEM ELECTRICAL
RATING
COMMENT COMMUNICATION
PARAMETERS
Mains supply
230V AC, 50Hz +10% - 15% (100 Watts maximum)
Standard
European
mains
connection
Mains supply fuse
T2A L250V
Replace only with similar type
Power supply rating
4 Amps including battery charge 28V +/- 2V
Maximum ripple current
200 millivolts
Battery type (Yuasa NP)
2 x 12 Volt sealed lead acid in series
Battery charge voltage
27.6VDC nominal (temperature compensated)
Modulated
DC
Battery charge current 1,5A
maximum
Modulated
DC
Current draw in mains fail condition 60 milliamps quiescent – 107 milliamps full alarm
Maximum current draw from
batteries
4 Amps
With main power source disconnected
Aux 24V output
Fused at 500mA with electronic fuse
200 milliamp maximum continuous load
1
st
and 2
nd
stage Sounder outputs
21 to 28V DC Fused at 1A with electronic fuse
1.0 Amp total load over all circuits
Voltage reversing DC
Fault relay contact rating
5 to 30VDC 1A Amp maximum for each
Maximum ratings not to be exceeded
Volt free changeover contact
Fire relay contact rating
5 to 30VDC 1A Amp maximum for each
Maximum ratings not to be exceeded
Volt free changeover contact
First stage contact rating
5 to 30VDC 1A Amp maximum for each
Maximum ratings not to be exceeded
Volt free changeover contact
Second stage contact rating
5 to 30VDC 1A Amp maximum for each
Maximum ratings not to be exceeded
Volt free changeover contact
Extract contact rating
5 to 30VDC 1A Amp maximum for each
Maximum ratings not to be exceeded
Volt free changeover contact
Terminal capacity
0.5mm
2
to 2.5mm
2
solid or stranded wire
Number of sounders per circuit
Dependent on type and current consumption
See table 2 for sounder types
Monitored input end of line
6K8 +/- 5% ½ Watt resistor
Supplied in terminals
Sounder circuit end of line
10K +/- 5% ¼ Watt resistor
Supplied in terminals
Extinguishing output end of line
1N4004 Diode
Supplied in terminals
No. of sounder circuits (2)
21 to 28V DC
1 x 1
st
stage and 1 x 2
nd
stage
Extinguishing release outputs (2)
21 to 28V DC. Fused at 1 Amp
1 Amp maximum load –for 5 minutes
3 Amps for 20 milliseconds
Voltage reversing DC with
calibration facility
Extinguishing release delay
Adjustable 0 to 60 seconds (+/- 10%)
5 second steps
Extinguishing release duration
Adjustable 60 to 300 seconds
5 second steps
Cabling
FP200 or equivalent (Maximum capacitance 1µF, max
inductance 1Mh)
Metal cable glands must be used
Monitored inputs normal threshold
(Allowable EOL)
10K ohm to 2K ohm
Monitored inputs alarm threshold
2K ohms to 150 ohms +/-5%
Monitored inputs s/c threshold
140 ohms to 0 ohms +/-5%
Status unit/Ancillary board
connection
Two wire RS485 connection (EIA-485 specification)
Maximum of 7 units per area- RS485
data cable.
(EIA-485 specification)
Status unit power output
21 to 28V DC, Fused at 500mA with electronic fuse
300 milliamp maximum load