X = the address of the disconnected ancillary board.
Turn the
ENABLE CONTROLS
keyswitch on and gently slide the
WRITE ENABLE
switch to the left.
The LCD will then display:
X = the address of the remaining status indicators
X = the address of the remaining ancillary boards
When the
ENTER
button is pressed on the module to which the status indicators or ancillary boards are
connected, the selected status indicator or ancillary board will be added to the system and the next unit
to be added will be displayed. Press the
ENTER
button on the ECU until all of the units have been
accepted then gently slide the
WRITE ENABLE
on the ECU switch to the right.
Full details of status units and ancillary boards can be found in TM202, TM203 and TM205.
13 Wiring to status units and ancillary boards
The ECU has terminals for data and power connections to FireBeta XT status indicator units and/or
ancillary boards. These terminals are labelled STATUS SERIAL and STATUS POWER. It is important to
wire these terminals with the correct polarity for both the serial data and power wiring.
FireBeta XT+ ECU
To next ancillary
board/Status
indicator