Press the
ENTER
button and the display will show:
To change setting, press the
ENTER
button.
To save the settings, slide the
WRITE ENABLE
switch gently to the right.
The released indicator will now be lit when the Extinguishing output operates.
14.8 Delay on manual release
The manual release function (panel mounted and remote) can be configured to have a pre-release time
delay (as per the set pre-release time) or to have no pre-release delay allowing immediate operation of
the Extinguishing output when a manual release is operated.
The factory default setting for this is for the manual release to have a delay time the same as the pre-
release delay.
To configure the module to have no delay when a manual release is operated, switch on the
ENABLE
CONTROLS
keyswitch and slide the
WRITE ENABLE
switch on the module to be configured gently to
the left. Press the
ENTER
button on the ECU then press the
UP
button until the display shows:
Press the
ENTER
button and the display will show:
To change to this, press the
ENTER
button.
To save the settings, slide the
WRITE ENABLE
switch gently to the right.
Operation of a manual release will now operate the Extinguishing outputs with no time delay.
14.9 Pre-release delay reset disabled
Once activated, an ECU can not be reset until after the reset inhibit time has expired and the
Extinguishing release timer has expired. It is possible to configure the module such that it can be reset
during the pre-release delay.
The factory default setting is for the pre-release delay reset to be disabled.
To configure the module such that it may be reset during the pre-release delay, switch on the
ENABLE
CONTROLS
keyswitch and slide the
WRITE ENABLE
switch on the module to be configured gently to
the left. Press the
ENTER
button on the ECU then press the
UP
button until the display shows:
Press the
ENTER
button and the display will show: