![Kidde 23911-K086 Скачать руководство пользователя страница 17](http://html1.mh-extra.com/html/kidde/23911-k086/23911-k086_operation-and-maintenance-manual_1965001017.webp)
TM206
17 of 35
Issue 1.0
ADDRESS SWITCH
POSITIONS
1
2
3
4
5
6
7
The address switch is located on the bottom left hand corner of the status indicator or ancillary PCB.
Note:
The address is only read when the boards are first powered or if the processor reset switch on the
ancillary board or status indicator is pressed, so address switches should not be altered on a system that
has power applied.
It is important that each individual status indicator and each ancillary board is allocated a unique address
in the range 1 to 7. Units of the same type with the same address will cause intermittent faults to be
displayed.
NOTE:
10 lamp status indicators (Part no’s 23911-K077, 23911-K078 and 23911-K082) are not compatible with
FireBeta XT+ ECU.
12.1 Adding new Status indicators/Ancillary boards
When the system is powered, it will search for connected status indicators and/or ancillary boards
connected to ECU.
If status indicators or ancillary boards are fitted and detected by the ECU, the LCD will display:
X = the number of faults
Press
ENTER
on the module to which the status indicators or ancillary boards are connected with the
ENABLE CONTROL
switch keyswitch off and use the
UP
button on the module to view the faults. If
status indicators and/or ancillary boards are detected the LCD will display:
X = the address of the status unit found
Or
X = the address of the ancillary board found