TM206
26 of 35
Issue 1.0
To invert the low pressure switch input, switch on the
ENABLE CONTROL
keyswitch and slide the
WRITE ENABLE
switch on the module to be configured gently to the left. Press the
ENTER
button on
the ECU then press the
DOWN
button until the display shows:
Press the
ENTER
button and the display will show:
To select this option, press the
ENTER
button.
To save the settings, slide the
WRITE ENABLE
switch gently to the right.
The low pressure switch input will now require a normally closed contact via a 470R trigger resistor and
6K8 end of line resistor for correct supervision.
14.15 Extinguishing output monitoring levels
The Extinguishing outputs are able to monitor both solenoid and igniting actuator releasing devices. To
do this the outputs must be calibrated with the releasing device and the cable, fitted as it will be in the
working system.
The Extinguishing outputs are fitted with a 1N4004 diode at the factory and the default monitoring level
will be set at approximately 206 but may be between 204 and 208.
To change the monitoring level for extinguishing output 2, switch on the
ENABLE CONTROL
keyswitch
and slide the
WRITE ENABLE
switch on the module to be configured gently to the left. Press the
ENTER
button on the ECU then press the
DOWN
button until the display shows:
Press the
ENTER
button and the display will show:
The XXX here will be the actual monitoring level read by the module.
To save this setting press the
ENTER
button.
To set the monitoring level for extinguishing output 1, press the
DOWN
button. The display will show:
Press the
ENTER
button and the display will show:
The XXX here will be the actual monitoring level read by the module.
To save this setting press the
ENTER
button.