TM206
29 of 35
Issue 1.0
Turn the
ENABLE CONTROL
keyswitch off to leave the disablement active. To re-enable the Released
relay output repeat the procedure above.
15.2.6 Disable Extract output
To disable the Extract relay output, press the
UP
button on the module while at access level 2 until the
display shows:
Press the
ENTER
button to select this function. The display will show:
The yellow disabled LED will be lit.
Turn the
ENABLE CONTROL
keyswitch off to leave the disablement active. To re-enable the Extract
relay output repeat the procedure above.
15.2.7 Turn on Extract output
To turn on the extract relay output, press the
DOWN
button on the module while at access level 2 until
the display shows:
Press the
ENTER
button to select this function. The display will show:
The yellow disabled LED on the module that has been disabled will be lit.
Turn the
ENABLE CONTROL
keyswitch off to leave the Extract output active. To turn off the Extract
output, repeat the procedure above.
Note:
The extract output does not turn off when the module is reset.
15.3 Single
input
activation
Upon activation of a single monitored activation input, the activated LED will flash, the 1
st
stage relay
contact will operate, the 1
st
stage sounder will operate and the LCD will show:
Pressing the Silence alarm button on the detection module will turn off the 1
st
stage sounder output.
15.4 Double
input
activation
Upon activation of a second monitored activation input with the ECU in Automatic/Manual mode with the
Hold inputs inactive and where the Disable Extinguishing function has not been invoked, the ECU will
respond as follows: