Testing the Heat Detector
1. Visually inspect the detector. Verify that the green LED flashes green.
2. Disconnect all releasing outputs per warnings on page 34.
3. Hold the heat gun (1200- to 1500-watt commercial hair blow dryer recommended) directed towards
the heat entry slots, maintaining a 6 in. (152 mm) minimum distance. Turn onto highest setting.
4. The detector should alarm within 10 to 15 seconds.
5. Verify that a detector activation indication is shown on the control unit.
6. Reset the system, and confirm that all alarm signals have cleared.
7. Once the alarms are cleared, and the system shows only trouble conditions for open releasing out-
puts, the releasing outputs can be re-connected to the system.
8. Once all releasing outputs have been reconnected, verify that all trouble conditions have been
cleared.
CAUTION
Do not apply excessive heat when using a heat gun or blow dryer. Excessive heat may damage
outer cover.
Содержание DS Series
Страница 1: ...K 73 200 Rev AB July 2015 DS Series Addressable Detector Application Guide K 76 1000 ...
Страница 2: ......
Страница 3: ...July 2016 1 K 76 1000 FOREWORD ...
Страница 6: ...K 76 1000 4 July 2016 NOTES ...
Страница 7: ...July 2016 5 K 76 1000 OVERVIEW ...
Страница 10: ...K 76 1000 8 July 2016 NOTES ...
Страница 11: ...July 2016 9 K 76 1000 HEAT DETECTOR SPACING ...
Страница 19: ...July 2016 17 K 76 1000 SMOKE DETECTOR SPACING ...
Страница 26: ...K 76 1000 24 July 2016 NOTES ...
Страница 27: ...July 2016 25 K 76 1000 HEAT DETECTOR APPLICATIONS ...
Страница 29: ...July 2016 27 K 76 1000 SMOKE DETECTOR APPLICATIONS ...
Страница 31: ...July 2016 29 K 76 1000 AIR DUCT SMOKE DETECTOR APPLICATIONS ...
Страница 35: ...July 2016 33 K 76 1000 TESTING AND MAINTENANCE ...
Страница 40: ...K 76 1000 38 July 2016 NOTES ...
Страница 41: ......