Stratification and Spacing Compensation
Stratification occurs when the upward movement of smoke and gases ceases due to the loss of buoyancy
of heated smoke. Stratified air within a room may impede smoke reaching the detector. To improve
detection system response in situations where stratification exists, install additional detectors at elevations
below ceiling level as shown in Figure 14. For additional information, refer to NFPA 72, Annex B.
Figure 14. Smoke Detector Compensation for Stratification
1. Ceiling section
2. Smoke detector, at ceiling
3. Smoke detector, below ceiling
4. Side view
5. Plan view
36 in. (910 mm) min.