Figure 16. Smoke Detector Location in Return Ducts
Duct Detector Mounting Plate (SIGA-DMP)
The SIGA-DMP Duct Detector Mounting Plate is a 7 in. (178 mm) square mounting plate with a 4 in. (100
mm) square electrical box used to directly mount a DS-PS smoke detector inside an air duct. The SIGA-
DMP includes screws for mounting the DS-SB or DS-RB detector base and a rubber gasket that forms an
airtight seal between the mounting plate and the air duct wall. See Figure 17 below.
Note:
Do not use with heat detectors.
Figure 17. The SIGA-DMP Duct Detector Mounting Plate for DS-PS Smoke Detector
•
Install the SIGA-DMP in ducts that have a maximum width and maximum height of 36 in. (910 mm).
•
The compatible smoke detector is the DS-PS. Compatible bases include the DS-SB and DS-RB.
•
Acceptable air velocity range is 300 - 4,000 ft./min (1.52 to 20.32 m/s).
1. Electrical box
2. Detector
3. Access panel door
4. Air duct
1
2
3
4
Содержание DS Series
Страница 1: ...K 73 200 Rev AB July 2015 DS Series Addressable Detector Application Guide K 76 1000 ...
Страница 2: ......
Страница 3: ...July 2016 1 K 76 1000 FOREWORD ...
Страница 6: ...K 76 1000 4 July 2016 NOTES ...
Страница 7: ...July 2016 5 K 76 1000 OVERVIEW ...
Страница 10: ...K 76 1000 8 July 2016 NOTES ...
Страница 11: ...July 2016 9 K 76 1000 HEAT DETECTOR SPACING ...
Страница 19: ...July 2016 17 K 76 1000 SMOKE DETECTOR SPACING ...
Страница 26: ...K 76 1000 24 July 2016 NOTES ...
Страница 27: ...July 2016 25 K 76 1000 HEAT DETECTOR APPLICATIONS ...
Страница 29: ...July 2016 27 K 76 1000 SMOKE DETECTOR APPLICATIONS ...
Страница 31: ...July 2016 29 K 76 1000 AIR DUCT SMOKE DETECTOR APPLICATIONS ...
Страница 35: ...July 2016 33 K 76 1000 TESTING AND MAINTENANCE ...
Страница 40: ...K 76 1000 38 July 2016 NOTES ...
Страница 41: ......