Figure 2 below shows that the square areas of coverage, A, B, and C, are all within the detector's circle of
coverage.
Figure 2. Heat Detector’s Circle of Coverage
Since all of the area within the detector’s circle of coverage is suitable for detecting a fire, the shape and
dimensions of the detector coverage “square” in Figure 3 may be modified. Note that, although the
coverage “square” is now a “rectangle,” the coverage area remains within the overall detector circle of
coverage.
Figure 3. Heat Detector Spacing, Rectangular Areas
1. Based on 50 ft. listed
spacing
Note: Smoke detectors are not listed for spacing
A
B
C
25 ft. x 34 ft. = 850
ft.² (7.6 m x 10.4 m = 79 m²)
20 ft. x 37 ft. = 740
ft.² (6.1 m x 11.3 m = 69 m²)
15 ft. x 39 ft. = 585
ft.² (4.6 m x 11.9 m = 54 m²)
10 ft. x 41 ft. = 410
ft.
² (3.1 m x 12.5 m = 38 m²)
30 ft. x 30 ft. = 900 ft.² (9.1 m x 9.1 m = 84 m²)
1
Содержание DS Series
Страница 1: ...K 73 200 Rev AB July 2015 DS Series Addressable Detector Application Guide K 76 1000 ...
Страница 2: ......
Страница 3: ...July 2016 1 K 76 1000 FOREWORD ...
Страница 6: ...K 76 1000 4 July 2016 NOTES ...
Страница 7: ...July 2016 5 K 76 1000 OVERVIEW ...
Страница 10: ...K 76 1000 8 July 2016 NOTES ...
Страница 11: ...July 2016 9 K 76 1000 HEAT DETECTOR SPACING ...
Страница 19: ...July 2016 17 K 76 1000 SMOKE DETECTOR SPACING ...
Страница 26: ...K 76 1000 24 July 2016 NOTES ...
Страница 27: ...July 2016 25 K 76 1000 HEAT DETECTOR APPLICATIONS ...
Страница 29: ...July 2016 27 K 76 1000 SMOKE DETECTOR APPLICATIONS ...
Страница 31: ...July 2016 29 K 76 1000 AIR DUCT SMOKE DETECTOR APPLICATIONS ...
Страница 35: ...July 2016 33 K 76 1000 TESTING AND MAINTENANCE ...
Страница 40: ...K 76 1000 38 July 2016 NOTES ...
Страница 41: ......