Regardless of the principle of operation, smoke detectors sense the presence of smoke particles. In order
for a smoke detector to sense these particles, smoke must travel from the point of origin to the detector.
When evaluating a particular building or location for detector layout, determine likely fire locations and
paths of smoke travel from each of these fire locations. Wherever practical, conduct actual field tests. The
most desired location for smoke detectors is the common points of intersection of smoke travel from fire
locations throughout the building. Ceiling height, construction, and ventilation play significant roles in
smoke detector performance.
The DS-PS photoelectric smoke detector has a wide range of fire sensing capabilities and is best suited
for detecting slow, smoldering fires such as wood pyrolysis and smoldering cotton.
Avoidance of False Alarms
Smoke detectors are sensitive to a number of environmental factors (other than smoke), which may
inadvertently activate the detectors. Careful consideration of the environment in which a detector is
installed minimizes unwanted detector activation (nuisance alarms). When locating smoke detectors,
consider common sources of false alarms:
•
Cooking equipment
•
Welding, cutting, and industrial processes
•
Chemical fumes
•
Dust
•
Engine exhaust
•
Vibration
•
Excessive airflow
•
Lightning and power outages
•
Lighting fixture and other electrical equipment that may emit noise/EMF
•
Radio frequency transmissions
•
Steam and moisture
Note:
The DS-PS smoke detector provides automatic environmental compensation, which reduces the
occurrence of false alarms by allowing sensing elements to adapt to long-term environmental
changes, caused by dirt, smoke, temperature, and humidity.
Table 4. Suitability of DS-PS Photoelectric Detector for Various Applications
Type of Fire
Suitability of detector
Open wood
Unsuitable
Wood pyrolysis
Optimal
Smoldering cotton
Optimal
PU foam
Very Suitable
N-heptane
Very Suitable
Liquid fire without smoke
Unsuitable
Содержание DS Series
Страница 1: ...K 73 200 Rev AB July 2015 DS Series Addressable Detector Application Guide K 76 1000 ...
Страница 2: ......
Страница 3: ...July 2016 1 K 76 1000 FOREWORD ...
Страница 6: ...K 76 1000 4 July 2016 NOTES ...
Страница 7: ...July 2016 5 K 76 1000 OVERVIEW ...
Страница 10: ...K 76 1000 8 July 2016 NOTES ...
Страница 11: ...July 2016 9 K 76 1000 HEAT DETECTOR SPACING ...
Страница 19: ...July 2016 17 K 76 1000 SMOKE DETECTOR SPACING ...
Страница 26: ...K 76 1000 24 July 2016 NOTES ...
Страница 27: ...July 2016 25 K 76 1000 HEAT DETECTOR APPLICATIONS ...
Страница 29: ...July 2016 27 K 76 1000 SMOKE DETECTOR APPLICATIONS ...
Страница 31: ...July 2016 29 K 76 1000 AIR DUCT SMOKE DETECTOR APPLICATIONS ...
Страница 35: ...July 2016 33 K 76 1000 TESTING AND MAINTENANCE ...
Страница 40: ...K 76 1000 38 July 2016 NOTES ...
Страница 41: ......