46
8. Problems with mains operation of Comfort control unit
8.2 Problems with mains operation / display
Flap cannot be closed
completely
during
start-up or by the “test”
key, i.e. the flap is
blocked by an object in
the backwater flap
“Flap fault”
- Wrong lever position
during cover fitting
Backwater detected.
The flap cannot be clo-
sed completely, howe-
ver, i.e. it is blocked by
an object, “Flap fault
during backwater”
Remove the mains plug, deac-
tivate the battery, open the Stau-
fix cover, eliminate the blockage
and return to operation
Recommendation:
Inform a specialist company
- See installation instructions
010-842 (section 4.2.1)
Close the emergency valve.
After the end of backwater, re-
move the blockage as described
Display
Cause Remedy
Notes
Battery is missing or
faulty
“Battery fault”
- Initialisation:
“Motor”
control cable is not
connected, connected
with inverse polarity or
is broken
- During operation:
“motor” control cable
faulty
“Motor fault”
- Initialisation:
“Probe”
control cable is not
connected, connected
with inverse polarity or
is broken
- During operation:
“Probe” control cable
faulty
“Probe faulty”
Remove the mains plug, connect
batteries, replace by new batte-
ries if necessary
When the unit is ready to func-
tion, a running light appears on
the display again.
Remove the mains plug, dis-
connect the battery; check the
control cable for correct connec-
tion or passage, replace motor if
necessary.
Remove the mains plug, deac-
tivate the battery; check the con-
trol cable for correct connection
or passage, replace probe if ne-
cessary.
- Initialisation:
The system can be
put into operation, i.e. it is functional.
Alarm can be acknowledged.
- Operation:
The fault message ap-
pears after a maximum of 5 minutes.
The system is ready for operation,
manual mode is possible.
Fault detection only takes place du-
ring operation (see chapter 8.2 “Ad-
ditional functions”).
- Initialisation:
Cannot be put into
operation
- During operation:
Fault detection
during manual operation test
cycle/backwater
The probe is scanned every 2 se-
conds.
Max. number of cy-
cles for flap exceeded
Motor transmitting fi-
gure exceeded
Replace motor
Inform the customer service
partner
Motor service life reached
Flap closes too often within a short
time
Caution:
Check position of the ope-
rating valve! The control attempts to
close the flap 3 x in the interval and
perhaps eliminate the blocking object
in the process. If the object can be re-
moved by the flap movement during
these cycles, the system is ready to
be used again. If this does not work,
the system switches to fault. Ackno-
wledgement of the acoustic signal is
possible. It is also possible to remove
the object by flushing the line. This
can be checked by pressing the test
key again. In the event of a negative
result, the fault message appears
again; the object must be removed as
described under remedial measures.
010-845EN_FKA_Schaltgerät_2011_03_010-131 Stand 10-07_AKTUELL2008.qxd 25.10.11 10:32 Seite 18
Содержание Staufix FKA Comfort
Страница 22: ...22 Notizen...
Страница 23: ...23 Notizen...
Страница 25: ......
Страница 27: ......
Страница 50: ...50 Notice 010 845EN_FKA_Schaltger t_2011_03_010 131 Stand 10 07_AKTUELL2008 qxd 25 10 11 10 32 Seite 22...
Страница 51: ...51 Notice 010 845EN_FKA_Schaltger t_2011_03_010 131 Stand 10 07_AKTUELL2008 qxd 25 10 11 10 32 Seite 23...
Страница 53: ...010 845EN_FKA_Schaltger t_2011_03_010 131 Stand 10 07_AKTUELL2008 qxd 25 10 11 10 32 Seite 25...
Страница 55: ...010 845EN_FKA_Schaltger t_2011_03_010 131 Stand 10 07_AKTUELL2008 qxd 25 10 11 10 32 Seite 27...
Страница 78: ...78 Note...
Страница 79: ...Note 79...