4.1 Control unit settings
4.1.1 General
The following functions are controlled by the control unit:
- Rinsing (Euro Norm grease separators do not have the rin-
sing function.)
- Heating
- Mixing
These functions are automatically started and ended accor-
ding to the programmed settings. The system’s components
can also be operated manually by using the control unit (See
Menu 2.1)
4.1.2 Programming the functions
The time of day, date and disposal program has been factory
set.
4.2 Operation
The control unit has a ‘Start’ and ‘Stop’ button (5) for ma-
nually controlling the disposal and a button for acknowled-
ging any alarms (3). The current operating status of the se-
parator is displayed by an LED (1), an alarm / malfunction
LED (2) and a function LED (4). The control unit can be ope-
rated by using the ‘Up
▲
’, ‘Down
▼
’, ‘ESC’ and ‘OK’ buttons (7).
Please follow the operating manual (8). Before conducting
any work on the control unit be sure to disconnect it from its
power source (9) (see safety instructions).
4.3
Functions / Steps of the disposal procedure
The control unit is set up for automated or manual operation.
Manual operation has the priority over automated operation. If
manual operation is activated, the automated operation is de-
activated (internally set automated procedures will not start!)
Note:
For proper disposal of collected grease, the heating fun-
ction should be run for at least 2 hours before disposal. During
the last minute of heating, the mixing motor should also run.
If the automated heating times are changed, the mixing
times should be changed accordingly.
4.4 Setting parameters
Note:
When programming the heating / mixing times be sure
that no times run into the next day. For example if heating
begins at 22:00 it should end at 23:59.
Setting the heating times
In Menu Section 3.1.1 the day on which heating should
occur can be set. Also here the starting time of the heating
and the duration of the heating can be set.
Setting the mixing function
Note: When programming the heating / mixing times be sure that
no times run into the next day. For example if heating begins at
22:00 it should end at 23:59.
Setting the rinsing function
In Menu 3.1.3 on the control unit the day of the week that rinsing
should take place can be set. Here you can also set the time of
day that the rinsing should begin and also the duration of the rin-
sing.
4. Operation
➀
➂
➄
➃
➅
➆
➇
➈
Operation – LED
Alarm-LED
Alarm – button
Pump operation – LED
START/STOP
Digital Display
Navigation buttons
‘Up/down’ + ‘ESC/OK’
Operating instructions
Disconnect control unit
from power
➁
0 System info
1 Information
2 Maintenance
3 Settings
2.1 Manual operation
2.2 Automated operation
2.3 SDS (Self Diagnosis System)
2.4 Service dates
2.5 Activating the Remote Control
3. Settings
3.1 Parameters
3.1.1.1 Every day
3.1.1.2 Monday
3.1.1.8 Sunday
3.1.1. ...........
3.1.1 Heating
3. Settings
3.1 Parameters
3.1.2 Duration
3.1.2 Mixing
3. Settings
3.1 Parameters
3.1.3.1 Every day
3.1.3.2 Monday
3.1.3.3 ..........
3.1.3.8 Sunday
3.1.3 Rinsing