The system must be checked once every month by the operator through observation of the switching routine for operatio-
nal ability and leaks.

8.1 General malfunctions

8. Malfunctions and troubleshooting

1

Pumps do not start 

Operating mode switch is not set to
"auto" (only up to model year 12/09)

Motor  protection  switch  has  trigge-
red, motor is blocked
Motor turns sluggishly
1 or 2 phases have no current

Control fails on account of heavy 
fluctuations  in  the  mains  power 
supply

Pressure  sensor  not  airtight  or  PE
hose not connected

Malfunction                             Cause                                                Remedial measure

Set switch to "auto"

Remove pump; eliminate blockage (object) in
the impeller or housing area

Maintenance / repair by Customer Services

Check fuses and power supply 
cables 
Retrofit battery in the switch unit and 
inform power supply company.

Check all screw connections for air-tightness

2

Pumps are running, 
Alarm level is reached /
is indicated

3

Pumps  run  roughly  or  loud

and  LED  "phase/rotary  field"
lights  up  (only  up  to  model
year 12/09))

3

Pumps  run  roughly  or  loud
and 

LED 

"phase/rotary

field" does not light up

(only

up to model year 12/09)

4

Wastewater  is  not  drained
off, backwater at the lowest
draining points

System is overloaded

Too little pumping capacity.

Aeration device not in operating position

Wrong  direction  of  rotation  for
motor

In the case of twin systems, both
motors are rotating the wrong way

Reduced 

capacity 

through 

damage

Wrong  direction  of  rotation  for
motor

In the case of twin systems, both
motors are rotating the wrong way

Systems not switched on

Power supply cable to the switch
unit without current

Level control malfunction

Inlet pipe to the system blocked

Check whether there is a short-term increase in
wastewater occurrence; if possible do not use
drainage points temporarily or divert wastewa-
ter elsewhere if possible

• Eliminate  object  in  the  impeller  or  housing

area

• Remove the object from the pressure fitting or

pressure pipe

• Pumps are worn, have them replaced
• Wrong lifting station design, clarification

through KESSEL Customer Services

Put aeration device into operating position

Check  direction  of  rotation,  if  incorrect  swap 
2 phases of the supply cable

Swap  2  phases  in  the  supply  cable  of  the 
switch unit

Check  pump(s)  and  motor(s);  have  damaged
parts replaced by Customer Services

Check the direction of rotation, if incorrect swap
2 phases of the motor supply cable (see sec-
tion 5.5)

Swap 2 phases of the motor supply cables of
the switch unit

Set switch to automatic

Check fuse. Check current supply.

Check soiling, switching points and function of
the level control

Clean inlet pipe

Содержание Aqualift F Standard

Страница 1: ...o Product advantages Simple connection through moulded connecting pieces Drilling surfaces for further connections Fully automatic operation Maintenance friendly PE tank General technical approval no...

Страница 2: ...chgear and the level control are under voltage and may not be opened Only electricians may work on the electrical equipment The term electrician is defined in the VDE 0105 Steps must be taken to ensur...

Страница 3: ...ise level is created that may be a nuisance depending on how the pump is installed If there are maximum noise level stipulations that need to be observed appropriate mea sures need to be taken The sou...

Страница 4: ...6 3 Operating the switch unit Page 18 6 4 Functional description Page 19 6 5 Functional test Page 19 7 Inspection and maintenance 7 1 Notes on the pump Page 20 7 2 Notes on aeration device Page 20 7...

Страница 5: ...entilation pipes at least DN 70 Wearing media must be kept away from the pump im peller The systems are suitable for constant wastewater tempera tures up to 35 C A maximum temperature of 60 C is per m...

Страница 6: ...100 order no 28647 28649 with non return valve DN100 110 DN70 75 DN32 40 DN100 110 475 Zulaufh he 180 3 1 2 Twin system 1 1 kW with pressure outlet DN 100 order no 28652 28659 with non return valve Tw...

Страница 7: ...g 7 x 1 5 mm2 Temperature of material pumped 35 C Weight pump 30 kg 31 kg Protective rating IP 68 24h 3m WS Operating mode S1 S3 Max period of perm operation 240 Min 30 duty cycler Sound level 70 db 7...

Страница 8: ...uit TF1 and TF2 b Up to model year 01 10 Level inputs each 15 8 V input approx 5 mA circuit TF or TF1 and TF2 and E7 or E7 and E8 for connecting the temperatu re switch of the pump motor sensor supply...

Страница 9: ...e system Such dama ge is not covered by the warranty 4 1 Fitting the collecting tank Umaintenance work on the lifting stations they must always be installed in such a way that there is sufficient acce...

Страница 10: ...out using connection clamps or rubber hoses with hose clamps To prevent the high tension forces leading to deformation at the connecting piece a suitable supporting ring must be pus hed into the upper...

Страница 11: ...pumping heights from 5 m Backwater flaps to avoid pressure blows for installation in the IMPORTANT In the case of all the connections drilled at the side it must be remembered that the level control i...

Страница 12: ...nected cables must be strain relieved Screw connections not used must always be sealed properly CAUTION Only qualified electricians may carry out the work on el ectrical equipment described below Befo...

Страница 13: ...d on the right at TF input wire 5 on the left at TF input Input E7 The jumper must be left Level inputs ON ALARM The cable must always be routed rising to the switch unit The cable ends of the pressur...

Страница 14: ...of the relays is prin ted on the board It means malfunction and alarm message is switched on The relay contacts do not have any internal connection to any kind of supply or operating voltages of the...

Страница 15: ...be left Input E8 The jumper must be left Level inputs ON ALARM The cable must always be routed rising to the switch unit The cable ends of the pressure level switch must be connected to the respectiv...

Страница 16: ...ot be used to switch different pha ses The phase may deviate from L1 however The malfunction and warning messages are issued via a relay changeover contact without protective circuit Inductive loads m...

Страница 17: ...off Anti blocking function off OFF up to year 12 09 5 6 Configuration of switch unit up to model year 12 09 Configuration of the control is carried out in the factory using switches S601 S604 between...

Страница 18: ...ch as metal sand etc Before initial operation the pump must be filled with pumping fluid up to the height of the ventilation bore hole of the pump housing The pump must not suck in any air After the c...

Страница 19: ...e other pump is switched on Parallel operation As the soiled water level rises in the tank the level switch on 1 closes After the on 1 switched has closed the switch on delay time begins see section 5...

Страница 20: ...return valve for function if appropriate The backwater flap must be replaced after 2 years of ope ration 7 1 Notes on the pump The pump should be checked at regular intervals If opera tional noises in...

Страница 21: ...the same type The contactor is a wearing part and should be checked and changed if necessary once a year if possible When chan ging the batteries make sure you dispose of them properly with the envir...

Страница 22: ...ed Too little pumping capacity Aeration device not in operating position Wrong direction of rotation for motor In the case of twin systems both motors are rotating the wrong way Reduced capacity throu...

Страница 23: ...ilar Backwater flap faulty wastewater runs out of the pressure pipe back into the system Foam formation in the system Tank or pumps are blocked by grease being discharged in large quantities Level con...

Страница 24: ...ust be acknowledged using the alarm key In the case of lifting stations jumper TF2 faulty not installed Replace install jumper Motor fault Duo Pump 1 Duo Pump 2 Running time limit fault running freque...

Страница 25: ...eck the air hose for leaks Rotary field phase fault Rotary field fault Wrong rotary field for mains connection of switch unit Swap 2 phases Phase fault Phase L1 or L2 L3 not available Check connection...

Страница 26: ...ing excee ded If the alarm level is exceeded both pumps switch on If the level drops below the on 2 level the pumps switch off Non closing on 2 level switch Malfunction message follows the alarm level...

Страница 27: ...ndicates this 8 2 3 Malfunction message SMalfunction messages are sent through Activation of the malfunction relay and thus through the warning device connected to this Display of the type of malfunct...

Страница 28: ...zeige Automatikbetrieb Niveau Anzeige leuchtet Pumpniveau erreicht Pumpen Anzeige leuchtet Pumpe l uft Unterdr cken des akustischen Alarms mit Taste Ausschalten Handbet tigen der Pumpe mit Taste g g g...

Страница 29: ...lfunction Phase rotary field red Permanently lit Phase failure has display priority for information for the Flashing Rotary field fault fitter motor protection Motor protection switch red Motor protec...

Страница 30: ...elec trician must always be consulted The current set at the motor protection switch must corre spond with the rated current of the connected motor and must not be adjusted by the operator Following...

Страница 31: ...31 9 2 2 Switch unit for single system from model year 12 09 9 Control unit Edition 04 99 Du EINZ F...

Страница 32: ...ivated Pump 2 green Pump output 2 activated Malfunction Phase rotary field red Permanently lit Phase failure has display priority for information for the Flashing Rotary field fault fitter motor prote...

Страница 33: ...33 9 3 2 Switch unit for double system Aqualift Duo up to model year 12 09 9 Control unit Edition 04 99 Du DUO F...

Страница 34: ...5 850118 DN 150 850119 Saw cap DN 50 DN 150 50100 Battery 1 unit from model year 01 2010 197 081 Rechargeable battery up to model year 12 2009 20230 Non return valve for mono systems DN 100 28683 Non...

Страница 35: ...mersible pipe 6 1 206 018 Cleaning cover 7a up to 12 09 1 206 048 Mono switch unit 1 1 kW 7a up to 12 09 1 206 116 Mono switch unit 2 2 kW 7b up to 01 10 1 363 100 Mono switch unit 1 1 kW 7b up to 01...

Страница 36: ...7a up to 12 09 1 206 117 Duo switch unit 2 2 kW 400 V 7b from 01 10 1 363 117 Duo switch unit 1 1 kW 400 V 7b from 01 10 1 363 118 Duo switch unit 2 2 kW 400 V 8 1 28663 Pressure hose D 110 x 6 for DN...

Страница 37: ...ingle system 206 017 Pos Unit Part No Description 1 1 28045 Pressure control unit mono 2 1 206 014 Upper part of pressure control unit 3 1 206 045 Cable screw connection 4 5m 206 047 Cable 5 2 017 153...

Страница 38: ...N 100 part no 240 051 Pos Unit Part No Description 1 1 240 046 Flap housing 2 1 240 048 Hose connection 110 3 1 240 038 Hex locknut M8 4 1 240 037 O Ring 5a 1 240 068 Backwater flap for 1 1 kW inc fla...

Страница 39: ...09 T piece DN 100 4a 2 240 068 Backwater flap for 1 1 kW inc flap stay 4b 2 240 069 Backwater flap for 2 2 kW inc flap stay 6 4 240 027 O Ring 7 8 240 058 Hexagon safety screw M6 8 8 240 059 Hexagon s...

Страница 40: ...SEL products are warranted for a period of 24 month This warranty period be gins on the day the product is shipped form KESSEL to its cu stomer The warranty only applies to newly manufactured products...

Страница 41: ...41...

Страница 42: ...erating instructions Initial operation and instruction were not carried out The client person responsible for initial operation was handed the following components and or product components Initial op...

Страница 43: ...______________________________ Contracted plumbing company __________________________________________________________ Address __________________________________________________________ Telephone Fax _...

Страница 44: ...ifting Stations and pumps K Drains and shower channels K Separators Grease Separators Oil Fuel Coalescence Separators Starch Separators Sediment Separators K Septic Systems K Inspection Chambers K Rai...

Отзывы: