background image

Technical Reference Manual – SB-293

Printing Date

01838-002 Rev. 3.0

July-1998

Page 13 of 32

Auxiliary RTE Input
One of the general-purpose inputs can be configured as an  auxiliary RTE input for the B-door. The
auxiliary RTE input allows a second RTE switch to be used to unlock the B-door at a controller. Using
a normally open switch as the input device, while the switch is in its normal state, the general-purpose
input circuit remains open. When a person requesting egress closes the switch, the general-purpose
input circuit is closed generating a state change. The controller then responds to this state change
per programmed instructions and generates a command to unlock the door and allow egress. Refer
to Figure 11 on page 19 for a typical auxiliary RTE input wiring diagram.

Output Relays

In many respects, a Form C output relay performs the opposite task of an input. An input detects a
state change generated by a device outside of the controller. An output relay receives a signal from
the controller that energizes the output relay, switching its state. This state change typically prompts
an action outside of the controller. The inputs drive the signals that control the output relays.

An example of this process is when a secure door is forced open. As the door is opened, the door
status switch opens. The door status switch input detects the switch's state change. The controller
sends a signal instructing the alarm relay to energize. The alarm relay switches its state to activate an
audio alarm notifying everyone in the immediate area that the door has been forced open. A variety of
devices may be activated by an output relay such as an electric door strike, a magnetic lock, an
alarm, a light, a video camera, or a modem.

A Form C relay has both normally closed and normally open circuits. When the relay is not energized,
the normally closed circuit is complete and the normally open circuit is open. When the relay is
energized the circuits switch roles; the normally open circuit is closed and the normally closed circuit
is open. This dual nature of Form C relays (having both normally closed and normally open circuits)
allows for two types of applications outside the controller. A device may be attached to the normally
closed circuit so that it is always on until the relay energizes to open the circuit and turn it off. Or, a
device may be attached to the normally open circuit so that it is always off until the relay energizes to
turn it on.

Lock Relay
Unlocking a door is controlled by the Form C lock relay. When installing a door lock there are two
things to consider: safety versus security, or should the door be "fail-safe" or "fail-secure."

Fail-safe means that if the power should fail at a door (perhaps due to a power outage or equipment
failure), the door will automatically unlock allowing entrance and egress. Power is required to keep
the door locked. A fail-safe door ensures people will be able to enter and exit a secured area through
that door in the case of an emergency.

A typical fail-safe application may use a magnetic lock. In this application, the controller energizes the
lock relay, causing the lock relay to change its state. In its new state the normally closed circuit is
opened breaking the power to the magnetic lock and allowing the door to be opened. Refer to Figure
6 on page 16 for a typical fail safe lock relay wiring diagram.

Fail-secure means that if the power should fail at a door (perhaps due to a power outage or
equipment failure), the door will automatically lock and not allow entrance but will continue to allow
egress. Power is required to unlock the door. A fail-secure door ensures a secured area remains
secure regardless of the situation.

A typical fail-secure application may use a door strike. In this application, the controller energizes the
lock relay, causing the lock relay to change its state. In its new state the normally open circuit is
closed activating the release mechanism for the door strike on the door to be opened. Refer to Figure
7 on page 17 for a typical fail secure lock relay wiring diagram.

SYSTEM INSTALLATION

Содержание SB-293

Страница 1: ...39 00 USD Keri Systems Technical Reference v3 0 SB 293 Satellite Board...

Страница 2: ...998 Keri Systems PXL 250 SB 293 Tiger Controller and Doors32 are trademarks of Keri Systems Inc Other product names are trademarks or registered trademarks of their owners Keri Systems Inc reserves th...

Страница 3: ...Open Relay 14 General Purpose Output Relay 14 Wiring Connections 15 Terminal Block Connections 15 Two Door Configuration 16 TB 7 Lock Relay Connection 16 TB 7 Alarm Relay Connection 17 TB 8 Door Stat...

Страница 4: ...wo Door Configuration 23 Normally Closed General Purpose Relay Output Connections Two Door Configuration 23 General Purpose Input Connections Additional I O Configuration 25 Normally Open General Purp...

Страница 5: ...ork including the SB 293 Satellite Board Standard features include Second Door Access Control Configuration two doors one reader per door in conjunction with a PXL 250 controller two door control inpu...

Страница 6: ...h and Request to Exit Inputs General Purpose Inputs Door Lock Output Relay 3A Form C Door Alarm Output Relay 3A Form C PXL 250 Tiger Controller Door Switch and Request to Exit Inputs General Purpose I...

Страница 7: ...ut Relays 2 Output Relays 6 General Purpose Inputs Lock Door Switch RTE B Door Alarm B 4 000 Feet Total Distance for Controller Network Communication PXL 250 Tiger Controller Door Switch and Request t...

Страница 8: ...0 Relative Humidity non condensing Controller Power Requirements 12 VDC 1 5 Amp Current Draw maximum current draw 500 mA for a controller with all options installed 120 mA max for a PXL 250 Controller...

Страница 9: ...proper operation of the access control system Under normal circumstances a 1 5KE39C transorb must be installed across the positive and negative power lines at the electric locking device to provide th...

Страница 10: ...onfigured for second door control the primary door must be connected to the A reader TB 5 on the PXL 250 controller board and the secondary door must be connected to the B reader TB 6 on the Receiver...

Страница 11: ...one output for the Alarm Relay Through programmable features in the Doors32 program the remaining two outputs can be dedicated to Door Held Open alarms for the A and B doors and one input can be dedic...

Страница 12: ...lly open input device that indicates when a change in state has occurred For a normally closed input device while the input device is in its normal state the general purpose input circuit remains clos...

Страница 13: ...circuits switch roles the normally open circuit is closed and the normally closed circuit is open This dual nature of Form C relays having both normally closed and normally open circuits allows for t...

Страница 14: ...es the output relay switching its state This state change typically initiates or ends an action outside of the controller A device may be attached to the relay s normally closed circuit so that it is...

Страница 15: ...e Figure 5 on page 16 Make a firm connection but be careful not to over tighten the screw Please note that all of the terminal blocks slide off the SB 293 Satellite Board should it become necessary to...

Страница 16: ...ections Figure 6 Fail Safe Lock Relay Output Connections For a typical fail secure door lock relay installation using a door strike refer to Table 2 and Figure 7 on page 17 and make the following wiri...

Страница 17: ...an set this output to door forced annunciation for the B door door forced annunciation on the A door is handled by the alarm out relay on the PXL 250 controller Door held open alarm annunciation is co...

Страница 18: ...nnections NOTE If a ground lead from the RTE input has already been installed on TB 8 pin 2 loosen the terminal connector and insert the door status switch ground lead beside the RTE input ground lead...

Страница 19: ...ellite Board must have been configured for two door operation for the auxiliary RTE input connections to be valid If the SB 293 board has been configured for general purpose inputs and outputs refer t...

Страница 20: ...Pin 2 ground common TB 9 Pin 2 ground common TB 9 Pin 3 general purpose signal GPI 6 TB 9 Pin 4 general purpose signal GPI 7 TB 9 Pin 5 ground common TB 9 Pin 5 ground common TB 9 Pin 6 general purpos...

Страница 21: ...93 satellite board Please refer to the Door Held Open Alarm Relay output section on page 14 for more information on Alarm relay outputs and output devices For a typical door held open alarm relay inst...

Страница 22: ...r this device can be attached to the relay s normally open circuit so that the device is always off until the relay energizes to turn it on Depending upon the type of device being installed and your a...

Страница 23: ...ormally Closed General Purpose Relay Output Connections Two Door Configuration TB10 1 2 3 4 5 6 Ground Common Normally Open Ground Common to TB 10 Pin 5 Normally Closed Signal to TB 10 Pin 6 Normally...

Страница 24: ...fer to Table 11 and Figure 17 on page 25 and make the following connections TB 8 TB 9 Pin Description TB 8 Pin 1 general purpose signal GPI 1 TB 8 Pin 2 ground common TB 8 Pin 2 ground common TB 8 Pin...

Страница 25: ...ypical general purpose relay installations refer to Table 12 and Figures 18 and 19 on page 26 and make the following wiring and transorb connections TB 7 TB 10 Pin Description TB 7 Pin 1 normally open...

Страница 26: ...neral Purpose I O Configuration TB10 1 2 3 4 5 6 Ground Common Normally Open Ground Common to TB 10 Pin 5 Normally Closed Signal to TB 10 Pin 6 Normally Closed Normally Open Signal to TB 10 Pin 4 NO C...

Страница 27: ...o the Doors32 User s Guide p n 01821 001 or to the on line help information found within the Doors32 program System Maintenance To ensure the best operating conditions for your access control system K...

Страница 28: ...ains electrical interference from data communication and power lines that support these electrical devices FAIL SAFE fail safe means that if the power should fail at a door the door will automatically...

Страница 29: ...o that it is always on until the relay energizes to open the circuit and turn it off Or a device may be attached to the normally open circuit so that it is always off until the relay energizes to turn...

Страница 30: ...lly Open 11 12 Request to Exit 12 REX See Request to Exit RTE See Request to Exit Inputs and Outputs 11 Installation Satellite Board 10 Wiring 11 Jumper Settings 10 Output Relays 13 Alarm Out 14 Door...

Страница 31: ...Technical Reference Manual SB 293 Printing Date 01838 002 Rev 3 0 July 1998 Page 31 of 32 Appendix 1 Quick Start Guide...

Страница 32: ...Technical Reference Manual SB 293 01838 002 Rev 3 0 Printing Date Page 32 of 32 July 1998 This page is intentionally left blank...

Страница 33: ...priate slot Firmly tighten the screw on the top of the terminal block but do not overtighten Quick Start Guide TB7 TB9 TB10 TB8 JP12 1997 MADE IN USA ASSY DESIGN6 UNIVERSAL OPTION BOARD REV C NO Lock...

Страница 34: ...C 0 to 90 Relative Humidity non condensing Controller Power Requirements 12 VDC 1 5 Amp Current Draw maximum current draw 500 mA for a controller with all options installed 120 mA max for a PXL 250 Co...

Страница 35: ...of the Satellite PCB with corresponding mounting holes in the controller PCB see the Satellite Controller Installation drawing below 4 Align the Satellite Board to Motherboard connector pins 5 Gently...

Страница 36: ...TB 9 Inputs Description TB 8 Pin 1 door status switch input normally closed TB 8 Pin 2 common ground TB 8 Pin 3 RTE input normally open TB 8 Pin 4 GPI 3 input 1 AUX RTE B input normally open TB 8 Pin...

Страница 37: ...nses motion and closes a circuit to create an input event at the controller TB8 1 2 3 4 5 6 Ground Common Signal Ground Common to TB 8 Pin 2 Signal to TB 8 Pin 3 Press Button to Close Circuit and make...

Страница 38: ...nd Common to TB 7 Pin 2 Normally Closed Signal to TB 7 Pin 3 Normally Closed Normally Open Signal to TB 7 Pin 1 12 VDC Power NO CONNECTION SB 293 LOCK RELAY FAIL SAFE 1 5KE39C Transorb for Transient S...

Страница 39: ...tion on the controller closes the normally open line sounding an alarm The following figure is for the A door The following figure is for the B door TB10 1 2 3 4 5 6 Ground Common Normally Open Ground...

Страница 40: ...event causes programming in the controller to open the normally closed line temporarily turning off a sensor device TB10 1 2 3 4 5 6 Ground Common Normally Open Ground Common to TB 10 Pin 2 Normally C...

Страница 41: ...2 normally closed line TB 10 Pin 1 GPO 3 normally open line TB 10 Pin 2 common ground TB 10 Pin 3 GPO 3 normally closed line TB 10 Pin 4 GPO 4 normally open line TB 10 Pin 5 common ground TB 10 Pin 6...

Страница 42: ...n a video camera TB8 1 2 3 4 5 6 Ground Common Signal Ground Common to TB 8 Pin 5 Signal to TB 8 Pin 6 Press Button to Open Circuit and Activate General Purpose Input Normally Closed Input Device TB9...

Страница 43: ...ed Relay Connection In the following application an event causes programming in the controller to open the normally closed line temporarily turning off a sensor device TB10 1 2 3 4 5 6 Ground Common N...

Страница 44: ...eone desires to exit through a secure door they press the RTE button closing the circuit and generating a state change The controller then responds to this state change and generates an output such as...

Отзывы: