background image

Technical Reference Manual – SB-293

01838-002 Rev. 3.0

Printing Date

Page 12 of 32

July-1998

controller then responds to this state change and generates an output (such as unlocking the door to
allow egress).

Door Status Switch Input
The door status switch input accepts a signal from a normally closed input switch that indicates the
status of the door: open or closed. While the door remains closed, the switch remains closed. When
someone opens the door, the door switch is opened, breaking the circuit and generating a state
change. The controller responds to this state change and generates an alarm output if the door is
forced or held open too long. Refer to Figure 9 on page 18 for a typical door status switch wiring
diagram.

NOTE: If the satellite board is configured for second door control and the door status switch is not
being used, install a jumper across pins 1 and 2 of TB-8 to prevent a continuous door open alarm
from being received by the controller.

NOTE: When using a door status input, the door must also have a Request to Exit input for proper
operation/annunciation of Door Forced and Door Held Open alarms.

Request to Exit
The request to exit (RTE) input accepts signals from a normally open input device that indicates that
a request has been made for someone to exit a secured door. Motion detectors, pressure-sensitive
floor mats, or push buttons may make RTE requests. While there is no one there to activate the RTE
request, the input remains open. When someone desires to exit through a secure door, they activate
the RTE device, closing the circuit and generating a state change. The controller then responds to
this state change and generates an output unlocking the door to allow egress. Refer to Figure 10 on
page 19 for a typical RTE wiring diagram.

General Purpose Inputs
The general-purpose input accepts signals from either a normally closed or a normally open input
device that indicates when a change in state has occurred.

For a normally closed input device, while the input device is in its normal state the general-purpose
input circuit remains closed. When the input device is activated, the general-purpose input circuit is
opened generating a state change. The controller may respond to this state change per programmed
instructions. The general-purpose input is configured through the 

Doors32™

 access control software.

A normally closed push-button may be used to provide a normally closed general-purpose input.
While the push button is in its normal state, the normally closed circuit is complete and no input signal
is generated at the controller. When a user presses the push button it opens the general-purpose
input circuit and generates a state change. The controller responds to this state change per
programmed instructions and may perform some action. Refer to either Figure 12 on page 20 or
Figure 16 on page 23 for a typical general-purpose normally closed input wiring diagram.

For a normally open input device, while the input device is in its normal state, the general-purpose
input circuit remains open. When the input device is activated, the general-purpose input circuit is
closed generating a state change. The controller may respond to this state change per programmed
instructions. The general-purpose input is configured through the 

Doors32™

 access control software.

A normally open motion detector may be used to provide a normally open general-purpose input. If
the motion detector does not detect motion, its alarm circuit remains open and no input signal is
generated at the controller. When the motion detector does detect someone entering its controlled
area, its alarm circuit closes, completing the general-purpose input circuit and generating a state
change. The controller responds to this state change per programmed instructions and may perform
some action. Refer to Figure 12 on page 20 or Figure 15 on page 23 for a typical general-purpose
normally open input wiring diagram.

SYSTEM INSTALLATION

Содержание SB-293

Страница 1: ...39 00 USD Keri Systems Technical Reference v3 0 SB 293 Satellite Board...

Страница 2: ...998 Keri Systems PXL 250 SB 293 Tiger Controller and Doors32 are trademarks of Keri Systems Inc Other product names are trademarks or registered trademarks of their owners Keri Systems Inc reserves th...

Страница 3: ...Open Relay 14 General Purpose Output Relay 14 Wiring Connections 15 Terminal Block Connections 15 Two Door Configuration 16 TB 7 Lock Relay Connection 16 TB 7 Alarm Relay Connection 17 TB 8 Door Stat...

Страница 4: ...wo Door Configuration 23 Normally Closed General Purpose Relay Output Connections Two Door Configuration 23 General Purpose Input Connections Additional I O Configuration 25 Normally Open General Purp...

Страница 5: ...ork including the SB 293 Satellite Board Standard features include Second Door Access Control Configuration two doors one reader per door in conjunction with a PXL 250 controller two door control inpu...

Страница 6: ...h and Request to Exit Inputs General Purpose Inputs Door Lock Output Relay 3A Form C Door Alarm Output Relay 3A Form C PXL 250 Tiger Controller Door Switch and Request to Exit Inputs General Purpose I...

Страница 7: ...ut Relays 2 Output Relays 6 General Purpose Inputs Lock Door Switch RTE B Door Alarm B 4 000 Feet Total Distance for Controller Network Communication PXL 250 Tiger Controller Door Switch and Request t...

Страница 8: ...0 Relative Humidity non condensing Controller Power Requirements 12 VDC 1 5 Amp Current Draw maximum current draw 500 mA for a controller with all options installed 120 mA max for a PXL 250 Controller...

Страница 9: ...proper operation of the access control system Under normal circumstances a 1 5KE39C transorb must be installed across the positive and negative power lines at the electric locking device to provide th...

Страница 10: ...onfigured for second door control the primary door must be connected to the A reader TB 5 on the PXL 250 controller board and the secondary door must be connected to the B reader TB 6 on the Receiver...

Страница 11: ...one output for the Alarm Relay Through programmable features in the Doors32 program the remaining two outputs can be dedicated to Door Held Open alarms for the A and B doors and one input can be dedic...

Страница 12: ...lly open input device that indicates when a change in state has occurred For a normally closed input device while the input device is in its normal state the general purpose input circuit remains clos...

Страница 13: ...circuits switch roles the normally open circuit is closed and the normally closed circuit is open This dual nature of Form C relays having both normally closed and normally open circuits allows for t...

Страница 14: ...es the output relay switching its state This state change typically initiates or ends an action outside of the controller A device may be attached to the relay s normally closed circuit so that it is...

Страница 15: ...e Figure 5 on page 16 Make a firm connection but be careful not to over tighten the screw Please note that all of the terminal blocks slide off the SB 293 Satellite Board should it become necessary to...

Страница 16: ...ections Figure 6 Fail Safe Lock Relay Output Connections For a typical fail secure door lock relay installation using a door strike refer to Table 2 and Figure 7 on page 17 and make the following wiri...

Страница 17: ...an set this output to door forced annunciation for the B door door forced annunciation on the A door is handled by the alarm out relay on the PXL 250 controller Door held open alarm annunciation is co...

Страница 18: ...nnections NOTE If a ground lead from the RTE input has already been installed on TB 8 pin 2 loosen the terminal connector and insert the door status switch ground lead beside the RTE input ground lead...

Страница 19: ...ellite Board must have been configured for two door operation for the auxiliary RTE input connections to be valid If the SB 293 board has been configured for general purpose inputs and outputs refer t...

Страница 20: ...Pin 2 ground common TB 9 Pin 2 ground common TB 9 Pin 3 general purpose signal GPI 6 TB 9 Pin 4 general purpose signal GPI 7 TB 9 Pin 5 ground common TB 9 Pin 5 ground common TB 9 Pin 6 general purpos...

Страница 21: ...93 satellite board Please refer to the Door Held Open Alarm Relay output section on page 14 for more information on Alarm relay outputs and output devices For a typical door held open alarm relay inst...

Страница 22: ...r this device can be attached to the relay s normally open circuit so that the device is always off until the relay energizes to turn it on Depending upon the type of device being installed and your a...

Страница 23: ...ormally Closed General Purpose Relay Output Connections Two Door Configuration TB10 1 2 3 4 5 6 Ground Common Normally Open Ground Common to TB 10 Pin 5 Normally Closed Signal to TB 10 Pin 6 Normally...

Страница 24: ...fer to Table 11 and Figure 17 on page 25 and make the following connections TB 8 TB 9 Pin Description TB 8 Pin 1 general purpose signal GPI 1 TB 8 Pin 2 ground common TB 8 Pin 2 ground common TB 8 Pin...

Страница 25: ...ypical general purpose relay installations refer to Table 12 and Figures 18 and 19 on page 26 and make the following wiring and transorb connections TB 7 TB 10 Pin Description TB 7 Pin 1 normally open...

Страница 26: ...neral Purpose I O Configuration TB10 1 2 3 4 5 6 Ground Common Normally Open Ground Common to TB 10 Pin 5 Normally Closed Signal to TB 10 Pin 6 Normally Closed Normally Open Signal to TB 10 Pin 4 NO C...

Страница 27: ...o the Doors32 User s Guide p n 01821 001 or to the on line help information found within the Doors32 program System Maintenance To ensure the best operating conditions for your access control system K...

Страница 28: ...ains electrical interference from data communication and power lines that support these electrical devices FAIL SAFE fail safe means that if the power should fail at a door the door will automatically...

Страница 29: ...o that it is always on until the relay energizes to open the circuit and turn it off Or a device may be attached to the normally open circuit so that it is always off until the relay energizes to turn...

Страница 30: ...lly Open 11 12 Request to Exit 12 REX See Request to Exit RTE See Request to Exit Inputs and Outputs 11 Installation Satellite Board 10 Wiring 11 Jumper Settings 10 Output Relays 13 Alarm Out 14 Door...

Страница 31: ...Technical Reference Manual SB 293 Printing Date 01838 002 Rev 3 0 July 1998 Page 31 of 32 Appendix 1 Quick Start Guide...

Страница 32: ...Technical Reference Manual SB 293 01838 002 Rev 3 0 Printing Date Page 32 of 32 July 1998 This page is intentionally left blank...

Страница 33: ...priate slot Firmly tighten the screw on the top of the terminal block but do not overtighten Quick Start Guide TB7 TB9 TB10 TB8 JP12 1997 MADE IN USA ASSY DESIGN6 UNIVERSAL OPTION BOARD REV C NO Lock...

Страница 34: ...C 0 to 90 Relative Humidity non condensing Controller Power Requirements 12 VDC 1 5 Amp Current Draw maximum current draw 500 mA for a controller with all options installed 120 mA max for a PXL 250 Co...

Страница 35: ...of the Satellite PCB with corresponding mounting holes in the controller PCB see the Satellite Controller Installation drawing below 4 Align the Satellite Board to Motherboard connector pins 5 Gently...

Страница 36: ...TB 9 Inputs Description TB 8 Pin 1 door status switch input normally closed TB 8 Pin 2 common ground TB 8 Pin 3 RTE input normally open TB 8 Pin 4 GPI 3 input 1 AUX RTE B input normally open TB 8 Pin...

Страница 37: ...nses motion and closes a circuit to create an input event at the controller TB8 1 2 3 4 5 6 Ground Common Signal Ground Common to TB 8 Pin 2 Signal to TB 8 Pin 3 Press Button to Close Circuit and make...

Страница 38: ...nd Common to TB 7 Pin 2 Normally Closed Signal to TB 7 Pin 3 Normally Closed Normally Open Signal to TB 7 Pin 1 12 VDC Power NO CONNECTION SB 293 LOCK RELAY FAIL SAFE 1 5KE39C Transorb for Transient S...

Страница 39: ...tion on the controller closes the normally open line sounding an alarm The following figure is for the A door The following figure is for the B door TB10 1 2 3 4 5 6 Ground Common Normally Open Ground...

Страница 40: ...event causes programming in the controller to open the normally closed line temporarily turning off a sensor device TB10 1 2 3 4 5 6 Ground Common Normally Open Ground Common to TB 10 Pin 2 Normally C...

Страница 41: ...2 normally closed line TB 10 Pin 1 GPO 3 normally open line TB 10 Pin 2 common ground TB 10 Pin 3 GPO 3 normally closed line TB 10 Pin 4 GPO 4 normally open line TB 10 Pin 5 common ground TB 10 Pin 6...

Страница 42: ...n a video camera TB8 1 2 3 4 5 6 Ground Common Signal Ground Common to TB 8 Pin 5 Signal to TB 8 Pin 6 Press Button to Open Circuit and Activate General Purpose Input Normally Closed Input Device TB9...

Страница 43: ...ed Relay Connection In the following application an event causes programming in the controller to open the normally closed line temporarily turning off a sensor device TB10 1 2 3 4 5 6 Ground Common N...

Страница 44: ...eone desires to exit through a secure door they press the RTE button closing the circuit and generating a state change The controller then responds to this state change and generates an output such as...

Отзывы: